Keypad Speaker Operation
When using LCD Keypads, the panel provides distinct speaker tones from the keypad for Fire, Burglary, Zone Monitor, and Prewarn events. The following describes the conditions when the keypad speaker turns on and off for each event:
|
Event |
Speaker Operation |
Description |
|---|---|---|
|
Fire |
ON |
Fire zone alarm and Bell Output or Fire Bell Output is ON |
|
OFF |
Alarm Silence |
|
|
Burglary |
ON |
Burglary zone alarm and Bell Output or Burglary Bell Output is ON |
|
OFF |
Alarm Silence |
|
|
Zone Monitor |
ON |
One time only when a monitored zone is tripped |
|
OFF |
After one tone |
|
|
Prewarn |
ON |
During Entry Delay |
|
OFF |
When Entry Delay expires |
Common Keypad Messages
|
Message |
Description |
Possible Solutions |
|---|---|---|
|
INVALID AREA |
A user has attempted door access for an area they are not assigned to. |
Change the user access areas if access to the area is needed. If access is not needed, the user cannot enter the area. |
|
INVALID CODE |
The user code entered is not recognized by the system. |
Check the user code and try again. |
|
INVALID GROUP |
A user attempted an action that is outside of their assigned group permissions. |
Check the group settings. See Groups. |
|
INVALID TIME |
The user code assigned to a specific schedule has been entered outside of the valid schedule. |
Check the schedule and user code settings. |
|
ENTER 2ND CODE |
The area a user is attempting to disarm or access is a Two Man Area. |
Enter a second and different user code. |
|
CLOSING TIME |
A schedule expired but the area is not armed. |
Users still on the premises should arm the system or extend the schedule to a later time. |
|
LATE TO CLOSE |
The system was not armed at its scheduled closing time. |
Users still on the premises should arm the system or extend the schedule to a later time. |
|
FAILED TO EXIT |
A user assigned the Anti-Passback permission has attempted to reenter an area where they did not exit properly. |
The user should exit the area through the proper door. If this is not possible, the system administrator should select Forgive in the User Codes menu. |
|
AC TROUBLE |
The system AC is low or missing. |
Check that all AC connections are good. |
|
BATTERY TROUBLE |
The system battery is low or missing. |
Check that all battery connections are good and the battery is still operational. |
|
SYSTEM TROUBLE or SERVICE REQUIRED |
There is a problem with one or more components in the system. |
Ensure the Reset jumper is removed from the panel, and there is not a short or open condition on the green data wire to the keypad. You may also need to check that all of the keypads and expansion modules on the bus are good. |
|
SYSTEM BUSY |
The system is performing another task with a higher priority. |
Wait a few moments for the system to complete the task. Ensure the Reset jumper is not on the panel. If the message displays for a long period of time, the processor could be locked up. |
|
4-WIRE BUS TROUBLE |
There is not a supervised device on the bus. |
Program a device to be supervised. |
|
There is low voltage or an open yellow wire. |
Ensure all wires are connected. |
|
|
Two devices share the same address |
Program one of the devices to a unique address. |
|
|
TRANSMIT FAIL |
The panel has attempted to communicate with the monitoring center 10 times and has not succeeded. |
Verify your communication type and account number. |
|
NON-POLLED ADDRESS |
The device is not programmed as Door, Keypad, or Fire in Device Setup. |
Program the device as Door, Keypad, or Fire in Device Setup. |
|
ENTER CODE (to enter the PROGRAMMER menu) |
A lockout code has been programmed for the panel. |
Enter the lockout code. |
|
WIRELESS TROUBLE |
The panel is unable to communicate with the wireless receiver. |
Verify the receiver is properly connected to the panel. Verify the correct House Code is programmed in System Options. Satisfy the front, rear, or both tampers. |
|
The wireless receiver’s tamper is faulted. |