This menu allows you to program areas and assign functions to each area in the system. Assign all non-24-hour zones to an area. See Zone Information.
Program the Panel at the Keypad
-
Press 6653 (PROG), then CMD at the keypad to enter the PROGRAMMER menu.
-
Press CMD until you see AREA INFORMATION, then press any select key or area.
-
Configure the following options as needed:
|
Keypad Display |
Description |
||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Exit Delay
EXIT DELAY: 60 |
Enter the exit delay time (0-250 seconds) for all Exit zone types in the area. The default is 60 seconds. When the Exit Delay time begins, activity from those zones and other non-24-hour zone types in the area is ignored until the delay expires. The keypad displays a countdown of the remaining Exit Delay time and sounds the Exit Delay tone at 8-second intervals. During the last 10 seconds, the tone sounds at 3-second intervals. If an Exit zone trips, restores, and trips again during the Exit Delay, the timer restarts. The timer can only restart once. Refer to Exit Error Operation for more information. |
||||||||||||||||||||
Closing Check
CLS CHK NO YES |
NO (default)—Disable this option. YES — Enable the panel to verify that all system areas are armed when a permanent or extended schedule expires. If any areas remain disarmed after the scheduled time, the keypads selected to display System Trouble messages display CLOSING TIME! and emit a steady beep. Programming Behavior
|
||||||||||||||||||||
Closing Code
CLS CODE NO YES |
NO (default) — Allow the system to be armed without a user code. YES — Require a user code to arm the system. |
||||||||||||||||||||
Any Bypass
ANY BYPS NO YES |
NO (default) — Disable this option. YES — Bypass zones without a user code during the arming sequence. Note: A user code is always required to use the Bypass Zones option from the menu. |
||||||||||||||||||||
Area Schedules
AREA SCH NO YES |
NO (default) — Areas follow only one set of schedules in the User Menu. YES — Allow each area to follow individual sets of area schedules programmed in the User Menu. |
||||||||||||||||||||
Early Morning Ambush
EARLY AMBUSH: 0 |
Enter the number of minutes (1-15) allowed between two valid user codes before a silent alarm (Early Morning Ambush) report is sent to the monitoring center using the Area 1 account number. Enter 0 to disable this option. When a user code is entered to disarm Area 1 at a keypad or reader with Access Areas assigned to Area 1, enter the same or a different user code within the programmed time to prevent the ambush report from being sent. The second user code also needs to have authority to disarm Area 1. Note: A zone activation with Alarm Action set to Message C also cancels the Early Morning Ambush timer and report from being sent to the receiver. The keypad does not display an indication while the timer is running. See Report to Transmit in Zone Information. Output Indications You can provide visual or other indications of the Early Morning Ambush timer by assigning outputs in Output Options:
|
||||||||||||||||||||
Area Number
AREA NO: - |
Enter the area number (1-99). |
||||||||||||||||||||
Area Name
*UNUSED* |
Enter an area name up to 32 alphanumeric characters. Inactive areas display as *UNUSED*. To mark an active area as unused, press any select key or area to clear the existing name, then press CMD. If Area Information was cleared in the Initialization menu, all areas automatically display as *UNUSED*. The following display name appear on the keypad:
|
||||||||||||||||||||
Opening/Closing Reports
O/C RPTS NO YES |
YES (default) — Send an Opening/Closing report to the receiver when the area is armed or disarmed. NO — Disable this option. |
||||||||||||||||||||
Automatic Arming
AUTO ARM NO YES |
NO (default) — Disable this option. YES — Automatically arm the area according to permanent, temporary, or extended schedules. If no schedules are programmed, the area auto arms every hour. When Closing Check is set to Yes, automatic arming occurs after the 10-minute Closing Check delay. If the area is disarmed outside of a permanent or temporary schedule, the Closing Check sequence begins one hour after the area is disarmed. Note: For ANSI/SIA CP-01 UL installations, automatic arming cannot be used for arming. |
||||||||||||||||||||
Bad Zones
BAD ZONES: BYP BYP FORC REF |
At the time of automatic arming, some zones in the area may not be in normal condition. This option determines how the panel handles zones that are in a bad condition during automatic arming.
|
||||||||||||||||||||
Automatic Disarming
AUTO DIS NO YES |
NO (default) — Disable this option. YES — Automatically disarm the area according to schedules. If an opening report is sent to the receiver, the user number is indicated as SCH. |
||||||||||||||||||||
Burglary Bell Output Number
BURG BEL OUT: 0 |
Enter the output number to activate when a Burglary zone goes into alarm. The output turns off when an area is disarmed and no other Burglary zones are in alarm. You can also turn off the output using Alarm Silence in the User Menu or by entering a user code with authority to silence alarms. The output remains on for the duration set in Bell Cutoff Time in Bell Options. The burglary bell output also activates for two seconds each time the system is armed. |
||||||||||||||||||||
Armed Output Number
ARMED OUTPUT: 0 |
Enter the output number to activate when the area is armed. If an exit delay is programmed for the area, the output turns on when the exit delay begins. The output turns off when the area is disarmed. Note: The Armed Output cannot be turned on using Outputs On/Off in the User Menu. |
||||||||||||||||||||
Late Output Number
LATE OUTPUT: 0 |
Enter the output number to activate when the area is not armed by its schedule time and Area Late or CLOSING TIME! displays on a keypad with the buzzer sounding. The output turns off when the keypad buzzer is silenced by pressing any key. The default is 0. |
||||||||||||||||||||
Late Arm Delay
LATE/ARM DLY: 60 |
Enter the number of minutes (4-250) that elapse before the area automatically re-arms after it is disarmed outside of a scheduled period. The default is 60 minutes. The Late Arm Delay can be overridden by the Rearm Delay setting in the User Group assigned to the user who disarmed the area. See Closing Check for more information. |
||||||||||||||||||||
Bank Safe & Vault
BANK/SAF NO YES |
NO (default) — Disable this feature. YES — Enable this option to prevent schedules for any area and time of day from being changed while the area is armed. Note: When enabled, the area can only be disarmed during scheduled times. Zones assigned to an area with this feature cannot be bypassed or force armed. Do not assign an area with this feature to an Arming zone, as Arming zones can disarm areas with this feature outside of a schedule. Program schedules before arming an area with this feature. If the area is armed before a schedule is programmed, reset the panel before disarming the area from a keypad, or set this option to No. |
||||||||||||||||||||
Common Area
COMMON NO YES |
NO (default) — Disable this option. YES — Enable the area as a common area. The area arms when the last area in the system is armed and disarms when the first area is disarmed. Note: Multiple common areas can be programmed in a system. Do not assign a common area to a user code. |
||||||||||||||||||||
Arm First Area
ARM FIRST NO YES |
NO (default) — Disable this option. YES — Enable the area as an Arm First area. The area automatically arms when any non-Arm First area assigned to the same keypad is armed. The area remains armed when other areas are disarmed. Note: Arm First automatic arming only occurs when arming from a keypad. Arming remotely or from a zone or schedule does not automatically arm Arm First areas. Multiple Arm First areas can be programmed in a system and assigned to different keypads using Display Areas in Device Setup. If an Arm First area has faulted zones that cannot be bypassed, arming stops and the areas are not armed. Correct the problem with the Arm First area, then begin the arming process again. |
||||||||||||||||||||
Dual Authority
DUAL AUTH: NO NO ARM DIS ALL |
Select the option that determines when two user codes are required to arm, disarm, or access doors in this area.
Enable Dual Authority for the appropriate user groups. When a user enters a code at a keypad to arm, disarm, or access a door in this area, 2ND CODE displays and a different user code with at least the same authority is required to be entered within 30 seconds. |
||||||||||||||||||||
Card Plus Pin
CARD+PIN NO YES |
This feature requires users to present a credential. YES (default) — Require a credential and 4-6 digit pin before submitting the specified action in the area. NO — Disable this option. All areas are defaulted to YES, while all groups are defaulted to NO. |
-
When you are finished, continue programming additional menus as needed, or press CMD until STOP displays, then press any select key or area to save the panel programming.
Program the Panel in Dealer Admin
Before You Begin
-
Verify the panel is connected to network
-
Log in to Dealer Admin.
-
Go to Customers, then select the System Name.
-
Go to Programming > Area Information.
-
Configure the following options as needed:
|
Dealer Admin Field |
Description |
|---|---|
Exit Delay
|
Enter the exit delay time (0-250 seconds) for all Exit zone types in the area. The default is 60 seconds. When the Exit Delay time begins, activity from those zones and other non-24-hour zone types in the area is ignored until the delay expires. The keypad displays a countdown of the remaining Exit Delay time and sounds the Exit Delay tone at 8-second intervals. During the last 10 seconds, the tone sounds at 3-second intervals. If an Exit zone trips, restores, and trips again during the Exit Delay, the timer restarts. The timer can only restart once. Refer to Exit Error Operation for more information. |
Closing Check
|
Toggle ON to enable the panel to verify that all system areas are armed when a permanent or extended schedule expires. If any areas remain disarmed after the scheduled time, the keypads selected to display System Trouble messages display CLOSING TIME! and emit a steady beep. Toggle OFF to disable this option. Programming Behavior
|
Closing Code
|
Toggle ON to require a user code to arm the system. Toggle OFF to allow the system to be armed without a user code. |
Any Bypass
|
Toggle ON to bypass zones without a user code during the arming sequence. Toggle OFF to disable this option. Note: A user code is always required to use the Bypass Zones option from the menu. |
Area Schedules
|
Toggle ON to allow each area to follow individual sets of area schedules programmed in the User Menu. Toggle OFF to allow areas to follow only one set of schedules in the User Menu. |
Early Morning Ambush
|
Enter the number of minutes (1-15) allowed between two valid user codes before a silent alarm (Early Morning Ambush) report is sent to the monitoring center using the Area 1 account number. Enter 0 to disable this option. When a user code is entered to disarm Area 1 at a keypad or reader with Access Areas assigned to Area 1, enter the same or a different user code within the programmed time to prevent the ambush report from being sent. The second user code also needs to have authority to disarm Area 1. Note: A zone activation with Alarm Action set to Message C also cancels the Early Morning Ambush timer and report from being sent to the receiver. The keypad does not display an indication while the timer is running. See Report to Transmit in Zone Information. Output Indications You can provide visual or other indications of the Early Morning Ambush timer by assigning outputs in Output Options:
|
Area Number
|
Select + Add Area, then enter the area number (1-99). |
Area Name
|
Enter an area name up to 32 alphanumeric characters. |
Automatic Arming
|
Toggle ON to automatically arm the area according to permanent, temporary, or extended schedules. If no schedules are programmed, the area auto arms every hour. Toggle OFF to disable this option. When Closing Check is set to Yes, automatic arming occurs after the 10-minute Closing Check delay. If the area is disarmed outside of a permanent or temporary schedule, the Closing Check sequence begins one hour after the area is disarmed. Note: For ANSI/SIA CP-01 UL installations, automatic arming cannot be used for arming. |
Bad Zones
|
At the time of automatic arming, some zones in the area may not be in normal condition. This option determines how the panel handles zones that are in a bad condition during automatic arming.
|
Automatic Disarming
|
Toggle ON to automatically disarm the area according to schedules. If an opening report is sent to the receiver, the user number is indicated as SCH. Toggle OFF to disable this option. |
Armed Output Number
|
Enter the output number to activate when the area is armed. If an exit delay is programmed for the area, the output turns on when the exit delay begins. The output turns off when the area is disarmed. Note: The Armed Output cannot be turned on using Outputs On/Off in the User Menu. |
Late Output Number
|
Enter the output number to activate when the area is not armed by its scheduled time. The output turns off when the area is armed or the keypad buzzer is silenced by pressing any key. The default is 0. |
Late Arm Delay
|
Enter the number of minutes (4-250) that elapse before the area automatically re-arms after it is disarmed outside of a scheduled period. The default is 60 minutes. The Late Arm Delay can be overridden by the Rearm Delay setting in the User Group assigned to the user who disarmed the area. See Closing Check for more information. |
Bank Safe & Vault
|
Toggle ON to enable this option to prevent schedules for any area and time of day from being changed while the area is armed. Toggle OFF to disable this feature. Note: When enabled, the area can only be disarmed during scheduled times. Zones assigned to an area with this feature cannot be bypassed or force armed. Do not assign an area with this feature to an Arming zone, as Arming zones can disarm areas with this feature outside of a schedule. Program schedules before arming an area with this feature. If the area is armed before a schedule is programmed, reset the panel before disarming the area from a keypad, or set this option to No. |
Common Area
|
Toggle ON to enable the area as a common area. The area arms when the last area in the system is armed and disarms when the first area is disarmed. Toggle OFF to disable this feature. Note: Multiple common areas can be programmed in a system. Do not assign a common area to a user code. |
Arm First Area
|
Toggle ON to enable the area as an Arm First area. The area automatically arms when any non-Arm First area assigned to the same keypad is armed. The area remains armed when other areas are disarmed. Toggle OFF to disable this feature. Note: Arm First automatic arming only occurs when arming from a keypad. Arming remotely or from a zone or schedule does not automatically arm Arm First areas. Multiple Arm First areas can be programmed in a system and assigned to different keypads using Display Areas in Device Setup. If an Arm First area has faulted zones that cannot be bypassed, arming stops and the areas are not armed. Correct the problem with the Arm First area, then begin the arming process again. |
Dual Authority
|
Select the option that determines when two user codes are required to arm, disarm, or access doors in this area.
Enable Dual Authority for the appropriate user groups. When a user enters a code at a keypad to arm, disarm, or access a door in this area, 2ND CODE displays and a different user code with at least the same authority is required to be entered within 30 seconds. |
Burglary Bell Output Number
|
Enter the output number to activate when a Burglary zone goes into alarm. The output turns off when an area is disarmed and no other Burglary zones are in alarm. You can also turn off the output using Alarm Silence in the User Menu or by entering a user code with authority to silence alarms. The output remains on for the duration set in Bell Cutoff Time in Bell Options. The burglary bell output also activates for two seconds each time the system is armed. |
Opening/Closing Reports
|
Toggle ON to send an Opening/Closing report to the receiver when the area is armed or disarmed. Toggle OFF to disable this feature. |
Card Plus PIN
|
Toggle ON to require a credential and 4-6 digit pin before submitted the specified action in the area. Toggle OFF to disable this feature. All areas are enabled by default, while all groups are disabled by default. |
-
When you are finished, select one of the following options:
-
-
If you are finished with all programming — Select Send All Changes at the top of the screen. This sends all programming changes to the panel.
-
If you are finished programming Area Information only — Select the More icon
, then select Send Area Information. This only sends area programming changes to the panel.
-
Reference
Exit Error Operation
At arming, if an Entry/Exit zone remains faulted when the Exit Delay expires, one of the following sequences occurs:
Entry Delay 1 EX Zone Types
-
The bell sounds for the duration programmed in Bell Cutoff.
-
The Entry Delay begins and requires a valid user code to disarm the system.
-
If the system is not disarmed, a zone alarm and exit error are sent to the receiver.
Entry Delay 2-4 EX Zone Types
-
The zone is force armed, and a Zone Force Arm message is sent to the receiver.
-
An Exit Error report is sent to the receiver.
-
The bell sounds for the duration programmed in Bell Cutoff.