XR650 Installation and Programming Guide

Output Options

This menu allows you to program panel output options. The panel provides two Form C relays (outputs 1 and 2) and four switched-ground, open-collector outputs (outputs 3–6). You can expand the system with up to 500 additional relay outputs using the panel’s LX-Bus or multiple 716 Output Expander Modules. When using an 1100XH Series wireless receiver, up to 45 additional wireless outputs are also available.

Select from the following output numbers:

Output Numbers

Description

1-6

Onboard outputs

450-474

Slow response time wireless outputs
(activates within 15 seconds)

400-449

Key fobs

480-499

Fast response time wireless outputs
(activates within 1 second)

500-999

LX-Bus output, relay output, and zone expansion output

D01-D16

Keypad door strike relay for address 1-16

Refer to Device Addresses for all output numbers.

G1-G20

Output groups

Note: Wireless output response time is the time between a panel event and the activation of the wireless output. The output number determines whether the response is slow or fast.

Slow-response outputs extend battery life but may take up to 15 seconds to activate. Fast-response outputs activate within 1 second but may reduce battery life. Refer to the specific wireless output installation guide for battery life information.

Configure output response times in Output Information.

Program the Panel at the Keypad

  1. Press 6653 (PROG), then CMD at the keypad to enter the PROGRAMMER menu.

  2. Press CMD until you see OUTPUT OPTIONS, then press any select key or area.

  3. Configure the following options as needed:

Keypad Display

Description

Cutoff Output

CO OUTS: ------

Enter an output (1–6) to turn off automatically after the time specified in Cutoff Time.

To disable this option, clear the display and press CMD. Dashes appear when no outputs are selected.

Output Cutoff Time

CUTOFF TIME: 0

If a Cutoff Output from 1–6 is assigned, enter 1–99 minutes for the amount of time the output remains on.

Enter 0 for continuous output.

Communication Trouble Output

COM FAIL OUT: 0

Enter the output number to activate when network is the primary communication method and network communication fails after one minute.

When network communication is restored, this output automatically turns off. To manually turn the output off, disarm any area or select Off for the output number in Outputs On/Off in the User Menu.

Enter 0 to disable this output.

Panic Alarm Output

PANC ALM OUT: 0

Enter the output number to activate when any Panic zone type goes into alarm. The output turns off when all Panic zone types are restored and a sensor reset is performed.

Enter 0 to disable this output.

Wireless Outputs

  • The Panic Alarm Output is compatible with the 1118 Wireless Remote Indicator Light and the 1116 Wireless Relay Output to a Model 572 Indicator LED.

  • When a panic alarm occurs, the LED turns on steadily for five minutes, then turns off.

  • When a panic test is initiated from a keypad, the LED flashes quickly for five minutes.

  • For panic alarm applications, DMP recommends using a fast-response wireless output.

Ambush Output

AMBUSH OUT: 0

Enter the output number to activate when an ambush code is entered at a keypad. The output turns off when a sensor reset is performed.

Enter 0 to disable this output.

Entry Output

ENTRY OUT: 0

Enter the output number to activate when the entry delay begins. The output turns off when the area is disarmed or the entry delay time expires.

Enter 0 to disable this output.

Begin Exit Output

BEG EXIT OUT: 0

Enter the output number to activate when an exit delay begins. The output turns off when the area is disarmed or the entry delay expires.

Enter 0 to disable this output.

End Exit Output

END EXIT OUTPUT: 0

Enter the output number to activate when an exit delay ends. The output turns off when the system is disarmed.

Enter 0 to disable this output.

Ready Output

READY OUT: 0

Enter the output number to activate when all disarmed burglary zones are in a normal state. The output turns off when any disarmed burglary zone type is in a faulted state.

Enter 0 to disable this output.

Note: This output is not compatible with Cutoff Outputs.

Disarmed Output

DISARMED OUT: 0

Enter the output number to activate when all areas of the panel are disarmed. The output turns off when any area is armed.

Enter 0 to disable this output.

Late to Close Output

LATE CLS OUT: 0

Enter the output number to activate when a closing schedule expires. The output activates at the same time CLOSING TIME! displays at the keypad.

Enter 0 to disable this output.

Device Fail Output

DVC FAIL OUT: 0

Enter the output number to activate when an addressed device fails to respond to panel polling. The panel sends a Missing Device report to the receiver and stores the event.

The output turns off when the device responds to polling or is removed from system programming.

Enter 0 to disable this output.

Note: The Device Fail Output cannot be used if any addressed device is unsupervised.

Sensor Reset Output

SNSR RST OUT: 0

Enter the output to activate when a sensor reset is performed from a keypad. The output automatically turns off after five seconds.

Enter 0 to disable this output.

Closing Wait Output

CLS WAIT OUT: 0

Enter the output number to activate for approximately 4 seconds when Closing Wait is set to Yes and the panel successfully communicates the closing message during arming.

The output does not activate if the closing message fails to communicate.

Enter 0 to disable this output.

Arm-Alarm Output

ARM-ALRM OUT: 0

Enter the output number to activate when any area of the system is armed. If an alarm occurs and the keypad turns red, the output pulses and continues to pulse for approximately five minutes after the panel is disarmed.

Enter 0 to disable this output.

Supervisory Alarm Output

SUPV ALR OUT: 0

Enter the output number to activate when a Supervisory zone type goes into alarm. The output turns off when all Supervisory zone types return to normal.

Enter 0 to disable this output.

Lockdown Output

LOCKDOWN OUT: 0

Enter the output number to activate when a zone goes into alarm. The output turns off when a sensor reset is performed, as long as no other Lockdown zone types remain in alarm.

Enter 0 to disable this output.

Zone Monitor Output

ZN MNTR OUT: 0

Enter the output number to activate momentarily when a zone monitor tone is activated on keypads. This output does not activate when zone monitoring is disabled.

When a sensor reset is performed, the alert message is cleared from the Status List.

Enter 0 to disable this output.

  1. When you are finished, continue programming additional menus as needed, or press CMD until STOP displays, then press any select key or area to save the panel programming.

Program the Panel in Dealer Admin

Before You Begin

  • Verify the panel is connected to network

  • Log in to Dealer Admin.

  1. Go to Customers, then select the System Name.

  2. Go to Programming > Output Options.

  3. Configure the following options as needed:

Dealer Admin Field

Description

Cutoff Outputs

Enter an output (1–6) to turn off automatically after the time specified in Cutoff Time.

To disable this option, clear the display and press CMD. Dashes appear when no outputs are selected.

Output Cutoff Time

If a Cutoff Output from 1–6 is assigned, enter 1–99 minutes for the amount of time the output remains on.

Enter 0 for continuous output.

Communication Fail Output

Enter the output number to activate when network is the primary communication method and network communication fails after one minute.

When network communication is restored, this output automatically turns off. To manually turn the output off, disarm any area or select Off for the output number in Outputs On/Off in the User Menu.

Enter 0 to disable this output.

Panic Alarm Output

Enter the output number to activate when any Panic zone type goes into alarm. The output turns off when all Panic zone types are restored and a sensor reset is performed.

Enter 0 to disable this output.

Wireless Outputs

  • The Panic Alarm Output is compatible with the 1118 Wireless Remote Indicator Light and the 1116 Wireless Relay Output to a Model 572 Indicator LED.

  • When a panic alarm occurs, the LED turns on steadily for five minutes, then turns off.

  • When a panic test is initiated from a keypad, the LED flashes quickly for five minutes.

  • For panic alarm applications, DMP recommends using a fast-response wireless output.

Ambush Output

Enter the output number to activate when an ambush code is entered at a keypad. The output turns off when a sensor reset is performed.

Enter 0 to disable this output.

Entry Delay Output

Enter the output number to activate when the entry delay begins. The output turns off when the area is disarmed or the entry delay time expires.

Enter 0 to disable this output.

Begin Exit Output

Enter the output number to activate when an exit delay begins. The output turns off when the area is disarmed or the entry delay expires.

Enter 0 to disable this output.

End Exit Output

Enter the output number to activate when an exit delay ends. The output turns off when the system is disarmed.

Enter 0 to disable this output.

Ready Output

Enter the output number to activate when all disarmed burglary zones are in a normal state. The output turns off when any disarmed burglary zone type is in a faulted state.

Enter 0 to disable this output.

Note: This output is not compatible with Cutoff Outputs.

Disarmed Output

Enter the output number to activate when all areas of the panel are disarmed. The output turns off when any area is armed.

Enter 0 to disable this output.

Late to Close Output

Enter the output number to activate when a closing schedule expires. The output activates at the same time CLOSING TIME! displays at the keypad.

Enter 0 to disable this output.

Device Fail Output

Enter the output number to activate when an addressed device fails to respond to panel polling. The panel sends a Missing Device report to the receiver and stores the event.

The output turns off when the device responds to polling or is removed from system programming.

Enter 0 to disable this output.

Note: The Device Fail Output cannot be used if any addressed device is unsupervised.

Sensor Reset Output

Enter the output to activate when a sensor reset is performed from a keypad. The output automatically turns off after five seconds.

Enter 0 to disable this output.

Closing Wait Output

Enter the output number to activate for approximately 4 seconds when Closing Wait is set to Yes and the panel successfully communicates the closing message during arming.

The output does not activate if the closing message fails to communicate.

Enter 0 to disable this output.

Arm-Alarm Output

Enter the output number to activate when any area of the system is armed. If an alarm occurs and the keypad turns red, the output pulses and continues to pulse for approximately five minutes after the panel is disarmed.

Enter 0 to disable this output.

Supervisory Alarm Output

Enter the output number to activate when a Supervisory zone type goes into alarm. The output turns off when all Supervisory zone types return to normal.

Enter 0 to disable this output.

Lockdown Output

Enter an output (1–6) to turn off automatically after the time specified in Cutoff Time.

To disable this option, clear the display and press CMD. Dashes appear when no outputs are selected.

Zone Monitor Output

If a Cutoff Output from 1–6 is assigned, enter 1–99 minutes for the amount of time the output remains on.

Enter 0 for continuous output.

  1. When you are finished, select one of the following options:

    • If you are finished with all programming — Select Send All Changes at the top of the screen. This sends all programming changes to the panel.

    • If you are finished programming Output Options only — Select the More icon menu.png , then select Send Output Options. This only sends output programming changes to the panel.