This menu allows you to program panel output options. The panel provides two Form C relays (outputs 1 and 2) and four switched-ground, open-collector outputs (outputs 3–6). You can expand the system with up to 500 additional relay outputs using the panel’s LX-Bus or multiple 716 Output Expander Modules. When using an 1100XH Series wireless receiver, up to 45 additional wireless outputs are also available.
Select from the following output numbers:
Output Numbers
|
Description |
|---|---|
|
1-6 |
Onboard outputs |
|
450-474 |
Slow response time wireless outputs
|
|
400-449 |
Key fobs |
|
480-499 |
Fast response time wireless outputs
|
|
500-999 |
LX-Bus output, relay output, and zone expansion output |
|
D01-D16 |
Keypad door strike relay for address 1-16 Refer to Device Addresses for all output numbers. |
|
G1-G20 |
Output groups |
Note: Wireless output response time is the time between a panel event and the activation of the wireless output. The output number determines whether the response is slow or fast.
Slow-response outputs extend battery life but may take up to 15 seconds to activate. Fast-response outputs activate within 1 second but may reduce battery life. Refer to the specific wireless output installation guide for battery life information.
Configure output response times in Output Information.
Program the Panel at the Keypad
-
Press 6653 (PROG), then CMD at the keypad to enter the PROGRAMMER menu.
-
Press CMD until you see OUTPUT OPTIONS, then press any select key or area.
-
Configure the following options as needed:
|
Keypad Display |
Description |
|---|---|
Cutoff Output
CO OUTS: ------ |
Enter an output (1–6) to turn off automatically after the time specified in Cutoff Time. To disable this option, clear the display and press CMD. Dashes appear when no outputs are selected. |
Output Cutoff Time
CUTOFF TIME: 0 |
If a Cutoff Output from 1–6 is assigned, enter 1–99 minutes for the amount of time the output remains on. Enter 0 for continuous output. |
Communication Trouble Output
COM FAIL OUT: 0 |
Enter the output number to activate when network is the primary communication method and network communication fails after one minute. When network communication is restored, this output automatically turns off. To manually turn the output off, disarm any area or select Off for the output number in Outputs On/Off in the User Menu. Enter 0 to disable this output. |
Panic Alarm Output
PANC ALM OUT: 0 |
Enter the output number to activate when any Panic zone type goes into alarm. The output turns off when all Panic zone types are restored and a sensor reset is performed. Enter 0 to disable this output. Wireless Outputs
|
Ambush Output
AMBUSH OUT: 0 |
Enter the output number to activate when an ambush code is entered at a keypad. The output turns off when a sensor reset is performed. Enter 0 to disable this output. |
Entry Output
ENTRY OUT: 0 |
Enter the output number to activate when the entry delay begins. The output turns off when the area is disarmed or the entry delay time expires. Enter 0 to disable this output. |
Begin Exit Output
BEG EXIT OUT: 0 |
Enter the output number to activate when an exit delay begins. The output turns off when the area is disarmed or the entry delay expires. Enter 0 to disable this output. |
End Exit Output
END EXIT OUTPUT: 0 |
Enter the output number to activate when an exit delay ends. The output turns off when the system is disarmed. Enter 0 to disable this output. |
Ready Output
READY OUT: 0 |
Enter the output number to activate when all disarmed burglary zones are in a normal state. The output turns off when any disarmed burglary zone type is in a faulted state. Enter 0 to disable this output. Note: This output is not compatible with Cutoff Outputs. |
Disarmed Output
DISARMED OUT: 0 |
Enter the output number to activate when all areas of the panel are disarmed. The output turns off when any area is armed. Enter 0 to disable this output. |
Late to Close Output
LATE CLS OUT: 0 |
Enter the output number to activate when a closing schedule expires. The output activates at the same time CLOSING TIME! displays at the keypad. Enter 0 to disable this output. |
Device Fail Output
DVC FAIL OUT: 0 |
Enter the output number to activate when an addressed device fails to respond to panel polling. The panel sends a Missing Device report to the receiver and stores the event. The output turns off when the device responds to polling or is removed from system programming. Enter 0 to disable this output. Note: The Device Fail Output cannot be used if any addressed device is unsupervised. |
Sensor Reset Output
SNSR RST OUT: 0 |
Enter the output to activate when a sensor reset is performed from a keypad. The output automatically turns off after five seconds. Enter 0 to disable this output. |
Closing Wait Output
CLS WAIT OUT: 0 |
Enter the output number to activate for approximately 4 seconds when Closing Wait is set to Yes and the panel successfully communicates the closing message during arming. The output does not activate if the closing message fails to communicate. Enter 0 to disable this output. |
Arm-Alarm Output
ARM-ALRM OUT: 0 |
Enter the output number to activate when any area of the system is armed. If an alarm occurs and the keypad turns red, the output pulses and continues to pulse for approximately five minutes after the panel is disarmed. Enter 0 to disable this output. |
Supervisory Alarm Output
SUPV ALR OUT: 0 |
Enter the output number to activate when a Supervisory zone type goes into alarm. The output turns off when all Supervisory zone types return to normal. Enter 0 to disable this output. |
Lockdown Output
LOCKDOWN OUT: 0 |
Enter the output number to activate when a zone goes into alarm. The output turns off when a sensor reset is performed, as long as no other Lockdown zone types remain in alarm. Enter 0 to disable this output. |
Zone Monitor Output
ZN MNTR OUT: 0 |
Enter the output number to activate momentarily when a zone monitor tone is activated on keypads. This output does not activate when zone monitoring is disabled. When a sensor reset is performed, the alert message is cleared from the Status List. Enter 0 to disable this output. |
-
When you are finished, continue programming additional menus as needed, or press CMD until STOP displays, then press any select key or area to save the panel programming.
Program the Panel in Dealer Admin
Before You Begin
-
Verify the panel is connected to network
-
Log in to Dealer Admin.
-
Go to Customers, then select the System Name.
-
Go to Programming > Output Options.
-
Configure the following options as needed:
|
Dealer Admin Field |
Description |
|---|---|
Cutoff Outputs
|
Enter an output (1–6) to turn off automatically after the time specified in Cutoff Time. To disable this option, clear the display and press CMD. Dashes appear when no outputs are selected. |
Output Cutoff Time
|
If a Cutoff Output from 1–6 is assigned, enter 1–99 minutes for the amount of time the output remains on. Enter 0 for continuous output. |
Communication Fail Output
|
Enter the output number to activate when network is the primary communication method and network communication fails after one minute. When network communication is restored, this output automatically turns off. To manually turn the output off, disarm any area or select Off for the output number in Outputs On/Off in the User Menu. Enter 0 to disable this output. |
Panic Alarm Output
|
Enter the output number to activate when any Panic zone type goes into alarm. The output turns off when all Panic zone types are restored and a sensor reset is performed. Enter 0 to disable this output. Wireless Outputs
|
Ambush Output
|
Enter the output number to activate when an ambush code is entered at a keypad. The output turns off when a sensor reset is performed. Enter 0 to disable this output. |
Entry Delay Output
|
Enter the output number to activate when the entry delay begins. The output turns off when the area is disarmed or the entry delay time expires. Enter 0 to disable this output. |
Begin Exit Output
|
Enter the output number to activate when an exit delay begins. The output turns off when the area is disarmed or the entry delay expires. Enter 0 to disable this output. |
End Exit Output
|
Enter the output number to activate when an exit delay ends. The output turns off when the system is disarmed. Enter 0 to disable this output. |
Ready Output
|
Enter the output number to activate when all disarmed burglary zones are in a normal state. The output turns off when any disarmed burglary zone type is in a faulted state. Enter 0 to disable this output. Note: This output is not compatible with Cutoff Outputs. |
Disarmed Output
|
Enter the output number to activate when all areas of the panel are disarmed. The output turns off when any area is armed. Enter 0 to disable this output. |
Late to Close Output
|
Enter the output number to activate when a closing schedule expires. The output activates at the same time CLOSING TIME! displays at the keypad. Enter 0 to disable this output. |
Device Fail Output
|
Enter the output number to activate when an addressed device fails to respond to panel polling. The panel sends a Missing Device report to the receiver and stores the event. The output turns off when the device responds to polling or is removed from system programming. Enter 0 to disable this output. Note: The Device Fail Output cannot be used if any addressed device is unsupervised. |
Sensor Reset Output
|
Enter the output to activate when a sensor reset is performed from a keypad. The output automatically turns off after five seconds. Enter 0 to disable this output. |
Closing Wait Output
|
Enter the output number to activate for approximately 4 seconds when Closing Wait is set to Yes and the panel successfully communicates the closing message during arming. The output does not activate if the closing message fails to communicate. Enter 0 to disable this output. |
Arm-Alarm Output
|
Enter the output number to activate when any area of the system is armed. If an alarm occurs and the keypad turns red, the output pulses and continues to pulse for approximately five minutes after the panel is disarmed. Enter 0 to disable this output. |
Supervisory Alarm Output
|
Enter the output number to activate when a Supervisory zone type goes into alarm. The output turns off when all Supervisory zone types return to normal. Enter 0 to disable this output. |
Lockdown Output
|
Enter an output (1–6) to turn off automatically after the time specified in Cutoff Time. To disable this option, clear the display and press CMD. Dashes appear when no outputs are selected. |
Zone Monitor Output
|
If a Cutoff Output from 1–6 is assigned, enter 1–99 minutes for the amount of time the output remains on. Enter 0 for continuous output. |
-
When you are finished, select one of the following options:
-
-
If you are finished with all programming — Select Send All Changes at the top of the screen. This sends all programming changes to the panel.
-
If you are finished programming Output Options only — Select the More icon
, then select Send Output Options. This only sends output programming changes to the panel.
-