XR650 Installation and Programming Guide

System Reports

This menu allows you to configure specific system reports the panel sends to the receiver.

Program the Panel at the Keypad

  1. Press 6653 (PROG), then CMD at the keypad to enter the PROGRAMMER menu.

  2. Press CMD until you see SYSTEM REPORTS, then press any select key or area.

  3. Configure the following options as needed:

Keypad Display

Description

Abort Reports

ABORT NO YES

NO (default) — Do not send an alarm abort report.

YES — Send an alarm abort report to the receiver when an area is disarmed during Transmit Delay, before the alarm report is sent and while the Bell Cutoff Time has not expired. If another area remains armed with zones in alarm, an abort report is not sent.

Note: Abort reports are not sent for Fire, Fire Verify, or Supervisory zones.

Restoral Reports

RESTORAL: YES

NO YES DISARM

Select when the panel sends zone restoral reports to the monitoring receiver.

  • YES (default) — Send a restoral report when a zone restores from a trouble or alarm condition.

  • NO — Disable zone restoral reports. Zones continue to operate normally but do not send restoral reports.

  • DISARM — Send a restoral report for a non-24-hour zone when the zone is disarmed after restoring from a trouble or alarm condition. Restoral reports for 24-hour zones are sent as soon as the zone restores.

Bypass Reports

BYPASS NO YES

YES (default) — Send zone bypass, reset, and force arm reports to the receiver. The report includes the zone number, zone name, and the user name and number of the person operating the system. Reports are sent only when O/C User is set to YES for Receiver 1 or Receiver 2.

NO — Do not send zone bypass reports.

Schedule Change Reports

SCHD CHG NO YES

YES (default) — Send schedule changes to the receiver. The report includes the day, opening time, closing time, extended schedule time, and the user name and number of the person who made the change.

NO — Do not send schedule changes to the receiver.

Code Change Reports

CODE CHG NO YES

YES (default) — Send reports for user code additions, changes, and deletions to the receiver. The report includes the user name and number that was added or deleted and the user name and number of the person who made the change. Reports are sent only when O/C User is set to YES for Receiver 1 or Receiver 2.

NO — Do not send user code change reports.

Access Keypads

ACCESS KEYPADS:

*1 *2 *4 *4
*5 *6 *7 *8

*9 *10 *11 *12
*13 *14 *15 *16

Enter the keypad addresses (1-16) that send door access reports to the receiver. An asterisk indicates that the keypad is selected. Press CMD to display the next set of keypad addresses.

Each door access enabled on a selected keypad generates an access report. Keypads that are not selected continue to operate the door relay but do not send access reports. The report includes the user number, user name, keypad address, and device name.

Ambush

AMBUSH NO YES

YES — Send an ambush report whenever user code 1 is entered at a keypad.

NO (default) — Do not send the ambush report and allow user 1 to operate like any other user code.

Late to Open Minutes

LATE TO OPEN MINUTES: 0

Enter 1–240 minutes for the amount of time the system can remain armed after the scheduled opening time without sending a Late To Open message. If the system remains armed after the Late to Open minutes expire, a Late To Open message is sent to the monitoring center.

Enter 0 to disable this option. The default is 0.

Early to Close Minutes

EARLY TO CLOSE MINUTES: 0

Enter 1–240 minutes for the amount of time the system can be armed before the scheduled closing time. If the system is armed prior to the Early to Close minutes, an Early To Close message is sent to the monitoring center.

Enter 0 to disable this option. The default is 0.

System Info

SYSTEM INFO NO YES

NO (default) — Send the Serial 3 message without the panel family and serial number identifiers.

YES — Include the panel family and serial number as additional identifiers at the end of the Serial 3 message sent to the monitoring center. These identifiers help monitoring center operators identify the correct system if multiple panels unintentionally use the same account number.

Note: This feature requires an SCS-VR or an SCS-1R with an SCS-150 Main Processor Card running firmware version 108 (9/23/25).

  1. When you are finished, continue programming additional menus as needed, or press CMD until STOP displays, then press any select key or area to save the panel programming.

Program the Panel in Dealer Admin

Before You Begin

  • Verify the panel is connected to network

  • Log in to Dealer Admin.

  1. Go to Customers, then select the System Name.

  2. Go to Programming > System Reports.

  3. Configure the following options as needed:

Dealer Admin Field

Description

Abort Reports

Toggle ON to send an alarm abort report to the receiver when an area is disarmed during Transmit Delay, before the alarm report is sent and while the Bell Cutoff Time has not expired. If another area remains armed with zones in alarm, an abort report is not sent.

Note: Abort reports are not sent for Fire, Fire Verify, or Supervisory zones.

Toggle OFF to disable this option.

Zone Restoral Reports

Select when the panel sends zone restoral reports to the monitoring receiver.

  • Yes (default) — Send a restoral report when a zone restores from a trouble or alarm condition.

  • No — Disable zone restoral reports. Zones continue to operate normally but do not send restoral reports.

  • Disarm — Send a restoral report for a non-24-hour zone when the zone is disarmed after restoring from a trouble or alarm condition. Restoral reports for 24-hour zones are sent as soon as the zone restores.

Bypass Reports

Toggle ON to send zone bypass, reset, and force arm reports to the receiver.

The report includes the zone number, zone name, and the user name and number of the person operating the system. Reports are sent only when O/C User is set to YES for Receiver 1 or Receiver 2.

Toggle OFF to disable this option.

Schedule Change Reports

Toggle ON to send schedule changes to the receiver.

The report includes the day, opening time, closing time, extended schedule time, and the user name and number of the person who made the change.

Toggle OFF to disable this option.

Code Change Reports

Toggle ON to send reports for user code additions, changes, and deletions to the receiver.

The report includes the user name and number that was added or deleted and the user name and number of the person who made the change. Reports are sent only when O/C User is set to Yes for Receiver 1 or Receiver 2.

Toggle OFF to disable this option.

Access Keypads

Enter the keypad addresses (1-16) that send door access reports to the receiver.

Each door access enabled on a selected keypad generates an access report. Keypads that are not selected continue to operate the door relay but do not send access reports. The report includes the user number, user name, keypad address, and device name.

Ambush

Toggle ON to send an ambush report whenever user code 1 is entered at a keypad.

Toggle OFF to disable this option and allow user 1 to operate like any other user code.

Late to Open

Enter 1–240 minutes for the amount of time the system can remain armed after the scheduled opening time without sending a Late To Open message. If the system remains armed after the Late to Open minutes expire, a Late To Open message is sent to the monitoring center.

Enter 0 to disable this option. The default is 0.

Early to Close

Enter 1–240 minutes for the amount of time the system can be armed before the scheduled closing time. If the system is armed prior to the Early to Close minutes, an Early To Close message is sent to the monitoring center.

Enter 0 to disable this option. The default is 0.

System Information

Toggle ON to include the panel family and serial number as additional identifiers at the end of the Serial 3 message sent to the monitoring center. These identifiers help monitoring center operators identify the correct system if multiple panels unintentionally use the same account number.

Toggle OFF to send the Serial 3 message without the panel family and serial number identifiers.

Note: This feature requires an SCS-VR or an SCS-1R with an SCS-150 Main Processor Card running firmware version 108 (9/23/25).

  1. When you are finished, select one of the following options:

    • If you are finished with all programming — Select Send All Changes at the top of the screen. This sends all programming changes to the panel.

    • If you are finished programming System Reports only — Select the More icon menu.png , then select Send System Reports. This only sends report programming changes to the panel.