XR650 Installation and Programming Guide

Output Information

This menu allows you to program outputs and configure their settings.

Output Numbers

Description

1-6

Onboard outputs

450-474

Slow response time wireless outputs
(activates within 15 seconds)

400-449

Key fobs

480-499

Fast response time wireless outputs
(activates within 1 second)

500-999

LX-Bus output, relay output, and zone expansion output

D01-D16

Keypad door strike relay for address 1-16

Refer to Device Addresses for all output numbers.

G1-G20

Output groups

Program the Panel at the Keypad

  1. Press 6653 (PROG), then CMD at the keypad to enter the PROGRAMMER menu.

  2. Press CMD until you see OUTPUT INFORMATION, then press any select key or area.

  3. Configure the following options as needed:

Keypad Display

Description

Output Number

OUTPUT NUMBER

Enter the output number. For wireless output troubles to display at the keypad, specify the keypad address at the Auxiliary 1 Zones option in Status List programming.

Output Name

OUTPUT NAME

Enter the a 32-character alphanumerical name for the output number.

Output Real-Time Status

OUTPUT REAL-TIME STATUS
NO YES

NO (default) — Disable this option.

YES — Allow real-time status reports for a hardwired device, such as Output On, Off, Pulse, or Temporal to be sent using Entré, the API connection, and Dealer Admin.

Serial Number

SERIAL#: XXXXXXXX

ALREADY IN USE OUTPUT NO: XXX

📍 Displays if a Wireless House Code is programmed in System Options and the output number is for a wireless output

Enter the 8-digit serial number found on the wireless device.

Already In Use, along with the programmed output number, displays when the serial number is already programmed for another output.

Supervision Time

SUPRVSN TIME: 240

0 3 60 240

Note: The 3-minute supervision time is only available for 1135 Wireless Sirens.

Select the supervision time required for the wireless output. The default is 240 minutes.

The transmitter checks in at least once during this time or a missing condition is indicated for that zone. Enter 0 to configure an unsupervised transmitter.

When the panel is reset, a receiver is installed or powered down and powered up, programming is complete, the supervision timer restarts for all wireless outputs.

Trip With Panel Bell

TRIP WITH PANEL BELL
NO YES

📍 Displays if you are programming an 1135 Wireless Siren.

YES (default) — Enable the 1135 to follow the panel’s bell output cadence for the zone type and bell cutoff time up to 15 minutes.

NO — Disable this option.

  1. When you are finished, continue programming additional menus as needed, or press CMD until STOP displays, then press any select key or area to save the panel programming.

Program the Panel in Dealer Admin

Before You Begin

  • Verify the panel is connected to network

  • Log in to Dealer Admin.

  1. Go to Customers, then select the System Name.

  2. Go to Programming > Output Information.

  3. Configure the following options as needed:

Dealer Admin Field

Description

Output Number

Enter the output number. For wireless output troubles to display at the keypad, specify the keypad address at the Auxiliary 1 Zones option in Status List programming.

Output Name

Enter the a 32-character alphanumerical name for the output number.

Serial Number

📍 Displays if a Wireless House Code is programmed in System Options and the output number is for a wireless output

Enter the 8-digit serial number found on the wireless device.

Supervision Time

Note: The 3-minute supervision time is only available for 1135 Wireless Sirens.

Select the supervision time required for the wireless output. The default is 240 minutes.

The transmitter checks in at least once during this time or a missing condition is indicated for that zone. Enter 0 to configure an unsupervised transmitter.

When the panel is reset, a receiver is installed or powered down and powered up, programming is complete, the supervision timer restarts for all wireless outputs.

Trip With Panel Bell

📍 Displays if you are programming an 1135 Wireless Siren.

Toggle ON to enable the 1135 to follow the panel’s bell output cadence for the zone type and bell cutoff time up to 15 minutes.

Toggle OFF to disable this option.

Real-time Status

Toggle ON to allow real-time status reports for a hardwired device, such as Output On, Off, Pulse, or Temporal to be sent using Entré, the API connection, and Dealer Admin.

Toggle OFF to disable this option.

  1. When you are finished, select one of the following options:

    • If you are finished with all programming — Select Send All Changes at the top of the screen. This sends all programming changes to the panel.

    • If you are finished programming Output Information only — Select the More icon menu.png , then select Send Output Information. This only sends output changes to the panel.