Use this function to select which zone alarms, zone troubles, and system monitor troubles display at specified keypads. The Status List displays automatically when the keypad is not being used for another function and remains displayed until the user arms or disarms the system or selects a menu option.
The Status List alternates with the Armed Status display on keypad addresses selected in Armed Status in Menu Display. You can select which system monitor troubles and zone types appear in the Status List, as well as which keypad addresses display them.
Program the Panel at the Keypad
-
Press 6653 (PROG), then CMD at the keypad to enter the PROGRAMMER menu.
-
Press CMD until you see STATUS LIST, then press any select key or area.
-
Configure the following options as needed:
|
Keypad Display |
Description |
|---|---|
|
To select a keypad, enter its device number (keypad address). An asterisk appears next to each selected keypad address. Enter the number again to deselect it. Press CMD to display keypad addresses 9–16. |
|
Display Keypads
DISPLAY KEYPADS |
Enter the keypad addresses that display for each status item described in the following fields. To prevent a status item from displaying on any keypad, leave all keypad addresses blank. |
System Monitor Troubles
SYSTEM TROUBLES *1 *2 *3 *4
*9 *10 *11 *12
|
Enter the keypad addresses that display any System Monitor trouble. The system monitors include the following options:
When a System Monitor trouble occurs, the System Monitor name appears in the Status List, and the keypad's steady trouble buzzer sounds. Press any select key or area to silence the buzzer. The trouble remains in the Status List until the condition is restored. The trouble buzzer sounds again at 10:00 AM each day until the system trouble is cleared from the Status List. |
Fire Zones
FIRE ZONES: *1 *2 *3 *4
*9 *10 *11 *12
|
Enter the keypad addresses where you want Fire zone alarms to display. When a Fire zone trips, the keypad display turns red to indicate an alarm. There is no trouble indication. A sensor reset is required to clear the condition after the zone returns to a normal state. |
Burglary Zones
BURGLARY ZONES *1 *2 *3 *4
*9 *10 *11 *12
|
Enter the keypad addresses that display all burglary zone alarms and troubles. Burglary zones include Night, Day, and Exit zone types. Burglary zone troubles remain in the Status List until the zone restores. For burglary alarms, only the most recently tripped zone remains in the list. The alarm remains displayed until another burglary zone goes into alarm, any area of the system is disarmed, or 10 minutes pass without another alarm. This ensures the most recently tripped zone remains displayed during an active burglary, even if the zone has restored. The keypad buzzer sounds for one second when a burglary alarm occurs. You can further specify which keypad addresses display burglary zone events by entering the corresponding area number in Display Areas in Device Setup. |
Supervisory Zones
SPRVISORY ZONES: *1 *2 *3 *4
*9 *10 *11 *12
|
Enter the keypad addresses that display all Supervisory zone alarms and troubles. Supervisory zone alarms and troubles appear in the Status List and sound the keypad buzzer until a valid user code is entered at any keypad. If a trouble condition remains, the buzzer sounds again at 10:00 AM each day until the supervisory trouble is cleared from the Status List. |
Panic Zones
PANIC ZONES: 1 2 3 4
9 10 11 12
|
Enter the keypad addresses that display all Panic zone alarms and troubles. The panic zones appear in the Status List until a sensor reset is performed. The keypad sounds if Bell Action is enabled in Bell Options. |
Emergency Zones
EMERGENCY ZONES: 1 2 3 4
9 10 11 12
|
Enter the keypad addresses that display all Emergency zone alarms and troubles. The zone name appears in the Status List until the zone restores. The keypad does not sound for emergency alarms or troubles. |
Auxiliary 1 Zones
AUX 1 ZONES: 1 2 3 4
9 10 11 12
|
Enter the keypad addresses that display all Auxiliary 1 zone alarms and troubles. The zone name appears in the Status List until the zone restores. The keypad does not sound for auxiliary 1 alarms or troubles. You can further specify which keypad addresses display auxiliary 1 zone events by entering the corresponding area number in Display Areas in Device Setup. |
Auxiliary 2 Zones
AUX 2 ZONES: 1 2 3 4
9 10 11 12
|
Enter the keypad addresses that display all Auxiliary zone alarms and troubles. The zone name appears in the Status List until the zone restores. The keypad does not sound for auxiliary 2 alarms or troubles. You can further specify which keypad addresses display auxiliary zone events by entering the corresponding area number in Display Areas in Device Setup. |
Communication Trouble
COMM PATH TRBL:
|
|
-
When you are finished, continue programming additional menus as needed, or press CMD until STOP displays, then press any select key or area to save the panel programming.
Program the Panel in Dealer Admin
Before You Begin
-
Verify the panel is connected to network
-
Log in to Dealer Admin.
-
Go to Customers, then select the System Name.
-
Go to Programming > Status List Display.
-
Configure the following options as needed:
|
Dealer Admin Field |
Description |
|---|---|
System Trouble Status Monitors
|
Enter the keypad addresses that display any System Monitor trouble. All keypads addresses are entered by default. The system monitors include the following options:
When a System Monitor trouble occurs, the System Monitor name appears in the Status List, and the keypad's steady trouble buzzer sounds. Press any select key or area to silence the buzzer. The trouble remains in the Status List until the condition is restored. The trouble buzzer sounds again at 10:00 AM each day until the system trouble is cleared from the Status List. |
Fire Zone Keypads
|
Enter the keypad addresses where you want Fire zone alarms to display. When a Fire zone trips, the keypad display turns red to indicate an alarm. There is no trouble indication. A sensor reset is required to clear the condition after the zone returns to a normal state. |
Burglary Zone Keypads
|
Enter the keypad addresses that display all burglary zone alarms and troubles. All keypads addresses are entered by default. Burglary zones include Night, Day, and Exit zone types. Burglary zone troubles remain in the Status List until the zone restores. For burglary alarms, only the most recently tripped zone remains in the list. The alarm remains displayed until another burglary zone goes into alarm, any area of the system is disarmed, or 10 minutes pass without another alarm. This ensures the most recently tripped zone remains displayed during an active burglary, even if the zone has restored. The keypad buzzer sounds for one second when a burglary alarm occurs. You can further specify which keypad addresses display burglary zone events by entering the corresponding area number in Display Areas in Device Setup. |
Supervisory Zone Keypads
|
Enter the keypad addresses that display all Supervisory zone alarms and troubles. All keypads addresses are entered by default. Supervisory zone alarms and troubles appear in the Status List and sound the keypad buzzer until a valid user code is entered at any keypad. If a trouble condition remains, the buzzer sounds again at 10:00 AM each day until the supervisory trouble is cleared from the Status List. |
Panic Zone Keypads
|
Enter the keypad addresses that display all Panic zone alarms and troubles. The panic zones appear in the Status List until a sensor reset is performed. The keypad sounds if Bell Action is enabled in Bell Options. |
Emergency Zone Keypads
|
Enter the keypad addresses that display all Emergency zone alarms and troubles. The zone name appears in the Status List until the zone restores. The keypad does not sound for emergency alarms or troubles. |
Auxiliary 1 Zone Keypads
|
Enter the keypad addresses that display all Auxiliary 1 zone alarms and troubles. The zone name appears in the Status List until the zone restores. The keypad does not sound for auxiliary 1 alarms or troubles. You can further specify which keypad addresses display auxiliary 1 zone events by entering the corresponding area number in Display Areas in Device Setup. |
Auxiliary 2 Zone Keypads
|
Enter the keypad addresses that display all Auxiliary zone alarms and troubles. The zone name appears in the Status List until the zone restores. The keypad does not sound for auxiliary 2 alarms or troubles. You can further specify which keypad addresses display auxiliary zone events by entering the corresponding area number in Display Areas in Device Setup. |
Comm Path Trouble
|
|
-
When you are finished, select one of the following options:
-
-
If you are finished with all programming — Select Send All Changes at the top of the screen. This sends all programming changes to the panel.
-
If you are finished programming Status List only — Select the More icon
, then select Send Status List. This only sends status list programming changes to the panel.
-