This section allows you to configure the panel’s physical device configuration. You can install and address up to 16 supervised devices on the keypad bus. Additional devices can be added to the available LX-Buses. Programmable device types include Keypad, Door, Expander, Fire, 1100T, XR Panel, and V-PLEX.
Program the Panel at the Keypad
-
Press 6653 (PROG), then CMD at the keypad to enter the PROGRAMMER menu.
-
Press CMD until you see DEVICE SETUP, then press any select key or area.
-
Configure the following options as needed:
|
Keypad Display |
Description |
|---|---|
Card Formats
CARD FORMATS |
This feature allows you to program custom non-DMP cards. Refer to the 734 Access Control Module Installation and Programming Guide for a chart of commonly used card formats and their defaults. |
Format Number
FORMAT NO: |
Enter the card format number (1-8). |
Format Name
FORMAT NAME |
Enter the card format name. |
Wiegand Code Length
WIEGAND CODE
|
When using a custom credential, enter the total number of bits (1-255) to be received in Wiegand code, including parity bits. The default is 26 bits. Determine and program the starting position location and code length into the 734 Series module. |
Site Code Position and Length
SITE CODE POS: 1
|
Enter the site code start position (0-255) in the data string. The default is 1. Enter the number of characters (1-16) the site code contains. The default is 8. |
User Code Position and Length
USER CODE POS: 9
|
Enter the user code start bit position (0-255). The default is 9. Enter the number of user code bits (16-64). The default is 16. |
Require Site Code
REQUIRE SITE CODE?
|
NO — Disable this option. YES — Enable a site code. In addition to User Code verification, door access is only granted when any one site code programmed at the SITE CODE ENTRY option matches the site code received in the Wiegand string. |
Site Code 1-8
SITE CODE 1:
|
734 Series Modules — Program up to 8 eight-digit site codes. Any previously programmed site codes display. Dashes represent blank site codes. The default is blank. 734N/734N-POE Modules Only — Program up to 8 eight-digit site codes. Any previously programmed site codes display. The default for Site Code 1 is 127. The default for site codes 2-8 are blank. To delete an existing site code, press any select key or area. Enter a new site code or press CMD to leave the option blank and continue to the next site code. Repeat these steps to change, delete, or add up to 8 site codes. |
Number of User Code Digits
NO OF USER CODE
|
Enter a user code digit length (4-12). The number should match the user code number length used by the panel. The default is 5. Any selection above 5 digits requires entry of the custom card definitions with custom site and user code positions for the Wiegand string. When searching the bit string for the user code, the digits are identified and read from left to right |
Device Number
DEVICE NO:
|
Note: Wireless keypads and network door controllers are unable to occupy address 1. Enter the address of the device you are programming. The available addresses are 1-16 on the panel keypad bus and 500-599 on the LX-Bus. The valid range for Keypad and Expander devices is 1-16 on the keypad bus. The valid range for Door devices is 1-16 on the keypad bus and 501-961 on the AX-Bus. See the Device Addresses and 734 Zone Numbers chart for available addresses. See 734 Modules AX-Bus Operation for more information on AX-Bus functionality. |
Device Name
*UNUSED* |
Enter a device name up to 32 alphanumeric characters. To remove a device from the system, delete the device name by pressing any select key or area, then select CMD. |
Device Type (Keypad Bus Addresses)
TYPE: KEYPAD DOOR KPD EXP TLR PNL Device Type (AX-Bus Addresses)
TYPE: KEYPAD DOOR VPX EXP PNL |
Select one of the following device types for the selected device number.
|
1100T
1100T? NO YES TRANSMITTER
1100T FREQ:
|
The 1100T allows you to use compatible non-DMP (competitor) wireless with an XR650 panel. NO (default) — Disable this option. YES — Use an 1100T Wireless Translator. Valid device numbers are 2-16. An 1100T can only be programmed on keypad addresses. One 1100T Translator is programmable per XR650 panel. Enter the 1100T serial number, then select one of the following communication frequencies:
If an 1100T is programmed, complete the following steps:
|
Device Communication Type
DEVICE COMM TYPE
DEVICE COMM TYPE
|
KYPD-BUS — Select this option for devices connected to the keypad bus. AX-BUS — Select this option for addresses 501-964. WLS — Enable wireless communication for the device. NET — Select this option for devices that communicate over a network connection. If the panel uses a hardwired network connection, it supports up to 15 network keypads. Note: You can only enter the Programmer menu or disable the Programming Port on a hardwired keypad when connected to the keypad bus on an XR650 panel. |
Encryption
ENCRYPTED?
|
Note: When encryption is enabled for a single device on an AX-Bus, ensure all devices on that bus are encrypted. NO (default) — Disable this option. YES — Enable encryption for this device. |
XR Panel Serial Number
XR PANEL
|
Enter the 8-digit serial number for the secondary XR panel. |
Supervision Time
SUPERVSN TIME: 240 SELECT MINUTES:
|
Select the supervision time required for the device. The default is 240 minutes. Enter 0 to configure an unsupervised wireless keypad. The device checks in at least once during this time or if a missing condition is indicated for that device. |
Access Areas
ACCESS AREAS |
To select an area, enter the area number (1-99) using the digit keys on the keypad. When an area is selected, an asterisk appears next to the area number. Enter the number again to deselect the area. Note: Users should have matching access area numbers assigned to their code to receive a door access at this device. |
Egress Areas
EGRESS AREAS |
Use this option to detect Anti-Passback violations. Anti-Passback requires a user to properly exit (egress) an area they have previously accessed. If users do not exit through the proper card reader location, they are not granted access on their next attempts. To select an area, enter the area number (1-99) using the digit keys on the keypad. When an area is selected, an asterisk appears next to the area number. Enter the number again to deselect the area. |
Display Areas
DISPLAY AREAS |
This option allows the panel’s burglary activities to segment so that only specific areas and their associated operations appear at a particular keypad. This allows area control from specific keypads, as well as zone annunciation assigned to those areas. To select an area, enter the area number (1-99) using the digit keys on the keypad. When an area is selected, an asterisk appears next to the area number. Enter the number again to deselect the area. When Display Areas is left defaulted (all areas selected), Menu Display, and Status List items determine if zone alarms and troubles display at this device, regardless of area assignment. All system areas may be armed and disarmed from this device. See Display Areas Operation for more information. |
Strike Time
STIKE TIME: 5 |
Enter a door access time (1-250 seconds) when a keypad or access control device relay is activated. The default is 5 seconds. Enter 0 to activate the device relay with a toggle action. Magnetic locks or electric door strikes are connected to the relay and released for the length of the strike time. This allows the user to activate or deactivate the device relay each time a valid user code is entered. The device relay is activated or deactivated until a user code is entered again. |
Strike Delay
STRIKE DELAY: 0 |
Enter the number of minutes (0-9) to delay a door strike after a valid code is entered or a card read occurs. The default is 0. When a valid code or card read is received, the activation of the door strike is delayed for the number of minutes programmed. The standard door strike message is sent to the monitoring center receiver. During the delay, all subsequent codes entered or cards presented to the reader for a door strike are ignored and no record of the attempt is stored. |
Fire Exit
FIRE EXIT NO YES |
NO (default) — Disable this option. YES — Allow the door access relay at this address to release when Fire panic keys are pressed or a Fire zone alarm is in the Status List. The relay is reset when a Sensor Reset is performed to remove all Fire zone alarms from the Status List. |
Public Door
PUBLIC DR NO YES |
NO (default) — Disable this option. YES — Allow the device to send a lock command when a lockdown is initiated through the User Menu, a remote command, or a Panic or Holdup zone programmed to initiate a lockdown. |
Output Group
OUTPUT GROUP NO YES |
NO (default) — Disable this option. YES — Allow the output group (relays) assigned to the user group to turn ON when the device relay is activated for the programmed Strike Time. See Groups for more information. |
Schedule Override
OVERRIDE NO YES |
NO (default) — Disable this option. YES — Allow the schedule to be overridden by the system’s armed condition. This allows the door schedule’s ON time to be ignored when all areas assigned to Access Areas for the device are armed. If any areas becomes disarmed after the door’s scheduled ON time, the device output turns on. A door output that is on during a disarmed period automatically turns off when all Access Areas assigned to the device become armed, even if the scheduled OFF time has not been reached. This feature can be used to keep doors locked when a factory opens late or is forced to close early. Note: When Schedule Override is set to Yes and there are not areas programmed in Access Areas, the door schedule for that device does not work. Set Schedule Override to No or enter an area number in Access Areas. |
Auto Force Arm Device
AUTO FORCE ARM DEVICE?
|
NO (default) — Disable this option. The user is prompted to select areas and choose to force arm or bypass at arming and disarming. YES — Allow all Display Areas assigned to the device to automatically arm and force arm faulted zones at arming. If Closing Code is set to Yes, only the matching areas between the Display Areas and the user code’s authorized areas arm. When Yes is selected, all matching areas assigned to the user code and to the device are automatically disarmed. |
Door Real-Time Status
DOOR REAL-TIME STATUS?
|
NO (default) — Disable this option. YES — Send real-time door status messages to Entré, the API connection, and Dealer Admin accounts that are reporting for the device. Messages are sent when the panel turns the door relay on or off. |
Send Door Forced
SEND DOOR FORCED MESSAGE?
|
NO (default) — Disable this option. YES — Send the Forced Open (FO) real-time door status messages to Entré, the API connection, and Dealer Admin reporting when the door relay is off but the door zone has transitioned from its normal state. |
|
734 Options |
|
Program 734 Options
PROGRAM 734 OPTIONS?
|
NO (default) — Do not program 734 options. YES — Program a 734. |
Reader Protocol Type
READER PROTOCOL TYPE
READER PROTOCOL:
|
Note: To use the OSDP programming fields below, 734 Access Control Module firmware Version 108 is required. Select WIEGAND (default) or OSDP for the card reader protocol type. |
OSDP LED Control
LED CONTROL
|
NO (default) — Disable this option. YES — Enable reader LED operation. |
OSDP Passphrase
OSDP PASSPHRASE
|
The OSDP passphrase is programmed into the OSDP reader and is used to establish 128-bit AES encrypted two-way communication between the reader and panel. Enter a passphrase up to 16 alphanumeric characters. These characters are visible until CMD is pressed. Record this passphrase and store it in a secure location away from the panel and reader. After the passphrase is bonded to the panel, the passphrase cannot be changed in the reader or retrieved from XR programming. |
OSDP Buzzer Control
BUZZER CONTROL
|
NO (default) — Disable this option. YES — Enable built-in reader annunciation. |
OSDP Tamper Control
TAMPER CONTROL
|
NO (default) — Disable this option. YES — Enable tamper control for the panel. To test the OSDP tamper control, ensure the OSDP reader’s tamper is no longer satisfied and observe the tamper message at the keypad and the messages sent to the monitoring center. |
Activate Zone 2 Bypass
ACTIVATE ZONE 2 BYPASS?
|
NO (default) — Disable this option. Allow standard zone operation on zone 2. YES — Activate the bypass option. If the door being released by the 734 is protected (contact installed), you can provide a programmable bypass entry/exit time by connecting its contact wiring to zone 2 on the 734. When the onboard Form C relay activates and the user opens the door connected to zone 2, the zone bypasses for the number of seconds programmed in Zone 2 Bypass Time to allow the user to enter or exit. If zone 2 does not restore (door closed) within the programmed bypass time, the 734 piezo pulses during the last ten seconds. If the zone does not restore before the programmed time, the 734 ends the bypass and indicates the open or short zone condition to the panel. |
Zone 2 Bypass Time
ZONE 2 BYPASS TIME: 40 |
Enter the number of bypass seconds (20-250) that can elapse before the bypass timer expires. The default is 40 seconds. If the door remains open when the timer expires, a zone open/short is sent to the panel for zone 2. |
Relock on Zone 2 Change
RELOCK ON ZONE 2 CHANGE?
|
NO (default) — Disable this option. Leave the relay on for the door access time when zone 2 restores. YES — Turn the 734 relay off and relock the door when zone 2 changes states. |
Activate Zone 3 Request to Exit
ACTIVATE ZONE 3 REX?
|
NO (default) — Disable this option. Allow standard zone operation on zone 3. YES — Activate the zone 3 REX option. See Zone 3 Additional Operation for more information. |
Zone 3 REX Strike Time
ZN 3 REX STRIKE TIME: 5 |
Enter the number of REX seconds (5-250) to elapse. The default is 5 seconds. |
Activate Onboard Speaker
ACTIVATE ONBOARD SPEAKER?
|
NO (default) — Turn off the piezo for all operations. This does not affect remote annunciator open collector (RA) operation. YES — Enable the onboard piezo speaker for local annunciation. |
Card Options
CARD OPTIONS
|
|
Require Site Code
REQUIRE SITE CODE
|
NO (default) — Disable this option. YES — Use a site code. In addition to user code verification, door access is only granted when any one site code programmed at Site Code Entry matches the site code received in the Wiegand string. |
No Communication With Panel
NO COMM WITH PNL
LAST |
This feature defines the relay action when communication with the panel has not occurred for approximately ten seconds. Select one of the following options:
|
-
When you are finished, continue programming additional menus as needed, or press CMD until STOP displays, then press any select key or area to save the panel programming.
Program the Panel in Dealer Admin
Before You Begin
-
Verify the panel is connected to network
-
Log in to Dealer Admin.
-
Go to Customers, then select the System Name.
-
Go to Programming > Device Setup.
Note: To program Card Formats in Dealer Admin, go to Programming > Card Formats.
-
Configure the following options as needed:
|
Dealer Admin Field |
Description |
||||||
|---|---|---|---|---|---|---|---|
Device Number
|
Note: Wireless keypads and network door controllers are unable to occupy address 1. Enter the address of the device you are programming. The available addresses are 1-16 on the panel keypad bus and 500-599 on the LX-Bus. The valid range for Keypad and Expander devices is 1-16 on the keypad bus. The valid range for Door devices is 1-16 on the keypad bus and 501-961 on the AX-Bus. See the Device Addresses and 734 Zone Numbers chart for available addresses. See 734 Modules AX-Bus Operation for more information on AX-Bus functionality. |
||||||
Device Name
|
Enter a device name up to 32 alphanumeric characters. |
||||||
Device Type
|
Select one of the following device types for the selected device number.
|
||||||
Device Communication Type
|
Keypad Bus — Select this option for devices connected to the keypad bus. AX-Bus — Select this option for addresses 501-964. Wireless— Enable wireless communication for the device. Network — Select this option for devices that communicate over a network connection.
|
||||||
Display Areas
|
This option allows the panel’s burglary activities to segment so that only specific areas and their associated operations appear at a particular keypad. This allows area control from specific keypads, as well as zone annunciation assigned to those areas. Enter the area number (1-99). When Display Areas is left defaulted (all areas entered), Menu Display, and Status List items determine if zone alarms and troubles display at this device, regardless of area assignment. All system areas may be armed and disarmed from this device. See Display Areas Operation for more information. |
||||||
Auto Force Arm Device
|
Toggle OFF to disable this option. The user is prompted to select areas and choose to force arm or bypass at arming and disarming. Toggle ON to allow all Display Areas assigned to the device to automatically arm and force arm faulted zones at arming. If Closing Code is toggled ON, only the matching areas between the Display Areas and the user code’s authorized areas arm. When enabled, all matching areas assigned to the user code and to the device are automatically disarmed. |
||||||
1100T Wireless Frequency
|
Select one of the following communication frequencies for the 1100T:
If an 1100T is programmed, complete the following steps:
|
||||||
Serial Number
|
Enter the device serial number. |
||||||
Supervision Time
|
Select the supervision time required for the device. The default is 240 minutes. Enter 0 to configure an unsupervised wireless keypad. The device checks in at least once during this time or if a missing condition is indicated for that device. |
||||||
Access Areas
|
Enter the area number (1-99) using the digit keys on the keypad. Note: Users should have matching access area numbers assigned to their code to receive a door access at this device. |
||||||
Egress Areas
|
Use this option to detect Anti-Passback violations. Anti-Passback requires a user to properly exit (egress) an area they have previously accessed. If users do not exit through the proper card reader location, they are not granted access on their next attempts. Enter the area number (1-99) using the digit keys on the keypad. |
||||||
Strike Time
|
Enter a door access time (1-250 seconds) when a keypad or access control device relay is activated. The default is 5 seconds. Enter 0 to activate the device relay with a toggle action. Magnetic locks or electric door strikes are connected to the relay and released for the length of the strike time. This allows the user to activate or deactivate the device relay each time a valid user code is entered. The device relay is activated or deactivated until a user code is entered again. |
||||||
Strike Delay
|
Enter the number of minutes (0-9) to delay a door strike after a valid code is entered or a card read occurs. The default is 0. When a valid code or card read is received, the activation of the door strike is delayed for the number of minutes programmed. The standard door strike message is sent to the monitoring center receiver. During the delay, all subsequent codes entered or cards presented to the reader for a door strike are ignored and no record of the attempt is stored. |
||||||
Fire Exit Release
|
Toggle OFF to disable this option. Toggle ON to allow the door access relay at this address to release when Fire panic keys are pressed or a Fire zone alarm is in the Status List. The relay is reset when a Sensor Reset is performed to remove all Fire zone alarms from the Status List. |
||||||
Public Door
|
Toggle OFF to disable this option. Toggle ON to allow the device to send a lock command when a lockdown is initiated through the User Menu, a remote command, or a Panic or Holdup zone programmed to initiate a lockdown. |
||||||
Encrypted
|
Note: When encryption is enabled for a single device on an AX-Bus, ensure all devices on that bus are encrypted. Toggle OFF to disable this option. Toggle ON to enable encryption for this device. |
||||||
Output Group
|
Toggle OFF to disable this option. Toggle ON to allow the output group (relays) assigned to the user group to turn ON when the device relay is activated for the programmed Strike Time. See Groups for more information. |
||||||
Schedule Override
|
Toggle OFF to disable this option. Toggle ON to allow the schedule to be overridden by the system’s armed condition. This allows the door schedule’s ON time to be ignored when all areas assigned to Access Areas for the device are armed. If any areas becomes disarmed after the door’s scheduled ON time, the device output turns on. A door output that is on during a disarmed period automatically turns off when all Access Areas assigned to the device become armed, even if the scheduled OFF time has not been reached. This feature can be used to keep doors locked when a factory opens late or is forced to close early. Note: When Schedule Override is set to Yes and there are not areas programmed in Access Areas, the door schedule for that device does not work. Set Schedule Override to No or enter an area number in Access Areas. |
||||||
Door Real-Time Status
|
Toggle OFF to disable this option. Toggle ON to send real-time door status messages to Entré, the API connection, and Dealer Admin accounts that are reporting for the device. Messages are sent when the panel turns the door relay on or off. |
||||||
Send Door Forced
|
Toggle OFF to disable this option. Toggle ON to send the Forced Open (FO) real-time door status messages to Entré, the API connection, and Dealer Admin reporting when the door relay is off but the door zone has transitioned from its normal state. |
||||||
Program 734 Options
|
Toggle OFF to not program 734 options. Toggle ON to program a 734. |
||||||
|
734 Options |
|||||||
Reader Protocol
|
Note: To use the OSDP programming fields below, 734 Access Control Module firmware Version 108 is required. Choose one of the following options for the card reader protocol type:
|
||||||
OSDP Passphrase
|
The OSDP passphrase is programmed into the OSDP reader and is used to establish 128-bit AES encrypted two-way communication between the reader and panel. Enter a passphrase up to 16 alphanumeric characters. Record this passphrase and store it in a secure location away from the panel and reader. After the passphrase is bonded to the panel, the passphrase cannot be changed in the reader or retrieved from XR programming. |
||||||
Activate Zone 2 Bypass
|
Toggle OFF to disable this option. Toggle ON to activate the bypass option. If the door being released by the 734 is protected (contact installed), you can provide a programmable bypass entry/exit time by connecting its contact wiring to zone 2 on the 734. When the onboard Form C relay activates and the user opens the door connected to zone 2, the zone bypasses for the number of seconds programmed in Zone 2 Bypass Time to allow the user to enter or exit. If zone 2 does not restore (door closed) within the programmed bypass time, the 734 piezo pulses during the last ten seconds. If the zone does not restore before the programmed time, the 734 ends the bypass and indicates the open or short zone condition to the panel. |
||||||
Zone 2 Bypass Time
|
Enter the number of bypass seconds (20-250) that can elapse before the bypass timer expires. The default is 40 seconds. If the door remains open when the timer expires, a zone open/short is sent to the panel for zone 2. |
||||||
Relock on Zone 2 Change
|
Toggle OFF to disable this option. Leave the relay on for the door access time when zone 2 restores. Toggle ON to turn the 734 relay off and relock the door when zone 2 changes states. |
||||||
Activate Zone 3 Request to Exit
|
Toggle OFF to disable this option. Allow standard zone operation on zone 3. Toggle ON to activate the zone 3 REX option. See Zone 3 Additional Operation for more information. |
||||||
Zone 3 REX Strike Time
|
Enter the number of REX seconds (5-250) to elapse. The default is 5 seconds. |
||||||
Activate Onboard Speaker
|
Toggle OFF to turn off the piezo for all operations. This does not affect remote annunciator open collector (RA) operation. Toggle ON to enable the onboard piezo speaker for local annunciation. |
||||||
Card Options
|
Select one of the following card options:
|
||||||
Require Site Code
|
Toggle OFF to disable this option. Toggle ON to use a site code. In addition to user code verification, door access is only granted when any one site code programmed at Site Code Entry matches the site code received in the Wiegand string. |
||||||
User Code Digits
|
Enter a user code digit length (4-12). The number should match the user code number length used by the panel. The default is 5. Any selection above 5 digits requires entry of the custom card definitions with custom site and user code positions for the Wiegand string. When searching the bit string for the user code, the digits are identified and read from left to right |
||||||
No Communication With Panel
|
This feature defines the relay action when communication with the panel has not occurred for approximately ten seconds. Select one of the following options:
|
||||||
|
OSDP Options Send Device Setup, then Dealer Admin displays the connected reader information. |
|||||||
OSDP LED Control
|
Toggle OFF to disable this option. Toggle ON to enable reader LED operation. |
||||||
OSDP Buzzer Control
|
Toggle OFF to disable this option. Toggle ON to enable built-in reader annunciation. |
||||||
OSDP Tamper Control
|
Toggle OFF to disable this option. Toggle ON to enable tamper control for the panel. To test the OSDP tamper control, ensure the OSDP reader’s tamper is no longer satisfied and observe the tamper message at the keypad and the messages sent to the monitoring center. |
||||||
-
When you are finished, select one of the following options:
-
-
If you are finished with all programming — Select Send All Changes at the top of the screen. This sends all programming changes to the panel.
-
If you are finished programming Device Setup only — Select the More icon
, then select Send Device Setup. This only sends device programming changes to the panel.
-
Reference
734 Modules AX -Bus Operation
An AX-Bus operation is compatible with 734, 734N, and 734N-POE modules. Once a 734 address is programmed for the bus, the LX-Bus is automatically converted from a hardwired zone expansion bus to a hardwired AX-Bus, and the bus begins to operate in the following ways:
-
Each 734 module provides one door relay and four protection zones to connect switches, such as door and window contacts.
-
16 doors of access can be programmed per AX-Bus to a maximum of eighty 734 modules. See the table below for available addresses.
-
Any unused AX-Bus zone numbers can be programmed as wireless zones. Hardwired zone expansion modules, such as the 711, 714, and 715-16, are incompatible with bus operation and cannot be used.
-
Device Setup programming for AX-Bus addresses are automatically programmed as door types. Device Type, Communication Type, and Display Areas are not shown. Only 734 module programming is shown.
Device Addresses and 734 Series Zone Numbers
Note: The 734E only communicates through the AX-Bus and does not use the keypad bus. When a 734E is programmed on a bus, all devices connected to that bus only operate if they are encrypted.
Addressable expanders and door controllers identify themselves to the control panel using their programmed address, which allows the panel to uniquely identify each device. The device address determines the zone, output, or door controller numbers assigned during programming.
Refer to the tables below and the device’s installation guide for addressing information.
|
Keypad Bus |
|
|
Device Address |
Zones |
|
1 |
11-14 |
|
2 |
21-24 |
|
3 |
31-34 |
|
4 |
41-44 |
|
5 |
51-54 |
|
6 |
61-64 |
|
7 |
71-74 |
|
8 |
81-84 |
|
9 |
91-94 |
|
10 |
101-104 |
|
11 |
111-114 |
|
12 |
121-124 |
|
13 |
131-134 |
|
14 |
141-144 |
|
15 |
151-154 |
|
16 |
161-164 |
D = Device Address
Z = Zones
|
AX/LX-Bus |
|||||||||
|---|---|---|---|---|---|---|---|---|---|
|
D |
Z |
D |
Z |
D |
Z |
D |
Z |
D |
Z |
|
501 |
501-504 |
601 |
601-604 |
701 |
701-704 |
801 |
801-804 |
901 |
901-904 |
|
505 |
505-508 |
605 |
605-08 |
705 |
705-708 |
805 |
805-808 |
905 |
905-908 |
|
509 |
509-512 |
609 |
609-612 |
709 |
709-712 |
809 |
809-812 |
909 |
909-912 |
|
513 |
513-516 |
613 |
613-616 |
713 |
713-716 |
813 |
813-816 |
913 |
913-916 |
|
517 |
517-520 |
617 |
617-620 |
717 |
717-720 |
817 |
817-820 |
917 |
917-920 |
|
521 |
521-524 |
621 |
621-624 |
721 |
721-724 |
821 |
821-824 |
921 |
921-924 |
|
525 |
525-528 |
625 |
625-628 |
725 |
725-728 |
825 |
825-828 |
924 |
925-928 |
|
529 |
529-532 |
629 |
629-632 |
729 |
729-732 |
829 |
829-832 |
929 |
929-932 |
|
533 |
533-536 |
633 |
633-636 |
733 |
733-736 |
833 |
833-836 |
933 |
933-936 |
|
537 |
537-540 |
637 |
637-640 |
737 |
737-740 |
837 |
837-840 |
937 |
937-940 |
|
541 |
541-544 |
641 |
641-644 |
741 |
741-744 |
841 |
841-844 |
941 |
941-944 |
|
545 |
545-548 |
645 |
645-648 |
745 |
745-748 |
845 |
845-848 |
945 |
945-948 |
|
549 |
549-552 |
649 |
649-652 |
749 |
749-752 |
849 |
849-852 |
949 |
949-952 |
|
553 |
553-556 |
653 |
653-656 |
753 |
753-756 |
843 |
853-856 |
953 |
953-956 |
|
557 |
557-560 |
657 |
657-660 |
757 |
757-760 |
857 |
857-860 |
957 |
957-960 |
|
561 |
561-564 |
661 |
661-664 |
761 |
761-764 |
861 |
861-864 |
961 |
961-964 |
*The 734E only communicates through the AX-Bus and does not use the keypad bus. When a 734E is programmed on a bus, all devices connected to that bus only operate if they are encrypted.
Display Areas Operation
Allowed User Actions
The user actions require the matching areas be enabled in Arm/Disarm areas option in Groups programming. When an area is selected, the following user actions are allowed:
-
Arming or disarming of the area(s) selected from the ARM or DISARM menu
-
Alarm Silence for the selected areas
-
Zone Bypass of zones assigned to the selected areas
-
Zone Monitor of zone assigned to the selected areas
-
Shift schedule changes allowed for the selected areas
-
Closing Check Schedule Extend allowed for the selected areas
-
Door Schedules changes allowed for devices that have matching area as defined in Device Access Areas
-
Door On/Off Menu operation allowed for devices that have matching area as defined in Device Access Areas
Allowed Status Displays
When an area is chosen, the following displays are allowed:
-
Armed Status of the selected areas
-
Zone alarms and troubles for burglary type zones (NT, DY, EX, A1, A2) assigned to the selected areas
-
Late to Close status of the selected areas
-
Zone Status (normal/fault) of zones that are assigned to the selected areas
Options and Actions Unaffected
The following options are not affected by the Display Areas operation. The User Code authority level controls access to the following items:
-
Sensor Reset Menu
-
Outputs On/Off Menu
-
System Status Menu
-
System Test/Panic Test
-
User Groups
-
Forgive Anti-Passback
-
Service Request
-
Set System Time and Date
-
Display Events
Note: 24-hour zones display at keypads based on Status List programming only
Zone 3 Additional Operation
Optionally, you can connect a PIR (or other motion sensing device) or a mechanical switch to zone 3 to provide REX capability to the system.
When Zone 3 shorts, the onboard Form C relay activates for the programmed number of seconds. During this time, the user can open the protected door to start the programmed bypass entry/exit timer. After the programmed number of seconds, the relay restores the door to its locked state.
The 734 provides a bypass-only option for REX on zone 3. When zone 3 opens from a normal state, only a bypass occurs, and the onboard relay does not activate. This bypass-only option uses two methods of REX:
-
The first REX device provides the programmed bypass entry/exit timer.
-
The second REX device, or manual device such as a door knob, unlocks the door.
An example of the bypass-only configuration is a door to an office that is locked 24 hours a day. Users pass a REX motion detector positioned by the door to begin the programmed exit timer. Within the programmed number of seconds, the user then manually activates a second device, such as a REX device or manual door knob, to unlock the door. If the door is opened after the programmed number of seconds, the zone goes into alarm.