This menu allows you to program the panel bell output functions.
Program the Panel at the Keypad
-
Press 6653 (PROG), then CMD at the keypad to enter the PROGRAMMER menu.
-
Press CMD until you see BELL OPTIONS, then press any select key or area.
-
Configure the following options as needed:
|
Keypad Display |
Description |
|---|---|
Bell Cutoff Time
BELL CUTOFF: 15 |
Enter the maximum time (1 to 99 minutes) that the panel bell and bell output remain on. If the area is disarmed the cutoff time resets. Enter 0 to provide continuous bell output. The default is 15 seconds. |
Bell Output
BELL OUTPUT: 0 |
Enter the output number to follow the panel bell output operation for all action and off conditions. Enter 0 to disable this feature. |
Bell Action
BELL ACTION….. |
This field defines the bell output type for each zone alarms. Press CMD to display the default bell output for each zone type. Press the corresponding select key or area and enter one of the following options: N — No bell output (default) S — Steady Bell output P — Pulsed output For Panic or Holdup zones, enable this feature to latch the bell action to a keypad. Trouble conditions do not activate the bell output. |
Burglary Bell Action
BURGLARY TYPE: S |
This option defines the bell action for Burglary zone types and Exit Error output. The default is S. |
Supervisory Bell Action
SUPRVSRY TYPE: N |
This option defines the bell action for Supervisory zone types. The default is N. |
Panic Bell Action
PANIC TYPE: N |
This option defines the bell action for Panic and Holdup zone types. The default is N. |
Emergency Bell Action
EMERGNCY TYPE: N |
This option defines the bell action for Emergency zone types. The default is N. |
Auxiliary 1 Bell Action
AUXLRY 1 TYPE: N |
This option defines the bell action for Auxiliary 1 zone types. The default is N. |
Auxiliary 2 Bell Action
AUXLRY 2 TYPE: N |
This option defines the bell action for Auxiliary 2 zone types. The default is N. |
-
When you are finished, continue programming additional menus as needed, or press CMD until STOP displays, then press any select key or area to save the panel programming.
Program the Panel in Dealer Admin
Before You Begin
-
Verify the panel is connected to network
-
Log in to Dealer Admin.
-
Go to Customers, then select the System Name.
-
Go to Programming > Bell Options.
-
Configure the following options as needed:
|
Dealer Admin Field |
Description |
|---|---|
Bell Cutoff Time
|
Enter the maximum time (1 to 99 minutes) that the panel bell and bell output remain on. If the area is disarmed the cutoff time resets. Enter 0 to provide continuous bell output. The default is 15 seconds. |
Bell Output
|
Enter the output number to follow the panel bell output operation for all action and off conditions. Enter 0 to disable this feature. |
Burglary Bell Action
|
This option defines the bell action for Burglary zone types and Exit Error output. Select one of the following options:
|
Supervisory Bell Action
|
This option defines the bell action for Supervisory zone types. Select one of the following options:
|
Panic Bell Action
|
This option defines the bell action for Panic and Holdup zone types. Select one of the following options:
|
Emergency Bell Action
|
This option defines the bell action for Emergency zone types. Select one of the following options:
|
Auxiliary 1 Bell Action
|
This option defines the bell action for Auxiliary 1 zone types. Select one of the following options:
|
Auxiliary 2 Bell Action
|
This option defines the bell action for Auxiliary 2 zone types. Select one of the following options:
|
-
When you are finished, select one of the following options:
-
-
If you are finished with all programming — Select Send All Changes at the top of the screen. This sends all programming changes to the panel.
-
If you are finished programming Bell Options only — Select the More icon
, then select Send Bell Options. This only sends bell programming changes to the panel.
-