This menu allows you to program the operation of each protection zone used in the system. All protection zones are programmed using the same process.
Program the Panel at the Keypad
-
Press 6653 (PROG), then CMD at the keypad to enter the PROGRAMMER menu.
-
Press CMD until you see ZONE INFORMATION, then press any select key or area.
-
Configure the following options as needed:
|
Keypad Display |
Description |
|---|---|
Zone Number
ZONE NO: - |
Enter the zone number. Refer to the Zone Numbers Table for available zone numbers. |
Zone Name
*UNUSED* |
Enter a zone name up to 32 alphanumeric characters. The zone name can display on keypads during arming and disarming, so users do not need to memorize zone numbers. For a zone that is not part of the system, clear the zone name to mark it as *UNUSED*. Press any select key or area to clear the existing name, then press CMD. The name is automatically changed to *UNUSED*. If Zone Information was cleared in Initialization, the zone is automatically marked as *UNUSED*. |
Zone Location
ZONE LOCATION
|
If needed, enter a zone location name up to 32 characters that is separate from the zone name. Enter a description location for the zone, such as 2nd Floor East Wing. The zone location is only sent to the monitoring center to help dispatchers identify where an alarm is triggered and does not display at the keypad. |
Zone Type
ZONE TYPE: BLANK – – NT DY EX FI PN EM SV A1 A2 AR IN DB HU |
The panel has 13 default zone types for configuring common zone applications. All zone types except Arming can be customized. The zone type determines the panel response (Alarm Action) when a zone is opened or shorted. Depending on the zone type and its restrictions, up to 13 Alarm Action responses are available. When you assign a zone type to a zone, automatic alarm actions are made. Select one of the following zone types:
If you select Blank, Night, Day, Exit, Auxiliary 1, Auxiliary 2, or Arming as the zone type, assign the zone to an active area. If you select Fire, Panic, Holdup, Emergency, Supervisory as the zone type, it is a 24-hour zone that is always armed and no area assignment is needed. |
Arm/Disarm Areas
ARM/DIS AREAS |
Enter the areas that the zone controls. When the zone changes from normal to shorted, the programmed areas toggle between the armed or disarmed condition using the Style programming. When restored to normal, no action occurs. When the zone is opened from a normal (disarmed) state, a trouble is reported. When opened from a shorted (armed) state, an alarm is reported and the zone is disabled until you disarm the area(s) from a keypad, Virtual Keypad, or Remote Link computer. |
Area Number Assignment
AREA NO: - |
Enter the area number where the Night, Day, Exit, Auxiliary 1, Auxiliary 2, or Instant zone is assigned. Area numbers 1 to 32 can be assigned. |
Style
STYLE: TGL ARM DIS STEP MNT |
This option allows you to choose the style for the arming/disarming operation. Select one of the following styles:
|
Expander Serial Number
EXPANDER SERIAL# |
If you are using a zone expansion module, enter the 10-character serial number found on the module. Already In Use displays when the serial number is already programmed for another zone. |
Next Zone
NEXT ZN? NO YES |
NO — Make alterations to the Alarm Action for a zone. To program zones for wireless operation, select No. YES — End zone programming. |
Wireless
WIRELESS? NO YES |
NO (default) — Do not program a wireless zone. YES — Program a wireless zone. Note: Program a Wireless House Code in System Options before adding wireless zones in the system. The following wireless zone numbers can be programmed:
|
Competitor Wireless
COMP WLS? NO YES |
NO (default) — Do not program a competitor wireless zone. YES — Program a competitor wireless zone if you are using the 1100T Wireless Translator. Note: Program a Wireless House Code in System Options before adding wireless zones in the system. |
Competitor Wireless Serial Number
COMP WLS SRL #: - LRN |
If you are using an 1100T Wireless Translator, enter the 8-character serial number found on the wireless device. Once the signal is detected and read, the device serial number displays on the keypad screen. To transmit the serial number to the panel automatically, select LRN. When TRANSMIT NOW appears on the keypad, tamper the transmitter that is being paired. Once the panel has received the tamper signal, the serial number displays on the keypad. |
Alarm Action
ALARM ACTION…. DISARMED OPEN DISARMED SHORT ARMED OPEN ARMED SHORT |
This option allows you to change any Zone Type standard definitions. When the Zone Type is specified, the Alarm Action for that zone is stored in memory. This feature allows you to configure the action taken by the panel when the zone is opened while the area is disarmed. There are three actions to define:
Make these selections for the Disarmed Short, Armed Open, and Armed Short zone conditions. |
Report to Transmit
MSG: NONE A T L – D S C |
Select one of the alarm report options:
Note: UL requirements prevent the Alarm (A) and Trouble (T) action for Fire zone types from being changed.
|
Output Number
OUTPUT NO: 0 |
Enter any Relay Output number to be activated by a zone condition. The default is 0. The output can be activated regardless of the Report to Transmit and if the zone is programmed as local. An output activated by an armed zone is turned off when the zone area is disarmed by a user. |
Output Action
OUTPUT: NONE STD PLS MOM FOLW |
Select one of the following output actions to assign to the relay:
Note: After you make the selections in the sections above, the same three selections for Disarmed Short, Armed Open, and Armed Short display. If the zone is a 24-hour type, only the Armed Open and Armed Short conditions display. |
Swinger Bypass
SWGR BYP NO YES |
NO — Disable this option. YES — Allow the zone to be swinger bypassed by the panel according to the specifications programmed in Swinger Bypass Trips and Reset Swinger Bypass. The Bypass condition displays in the keypad Status List. If within one hour a zone trips the total number of times programmed in Swinger Bypass Trips, the panel bypasses it until the following conditions occur:
If the zone trips fewer than the specified times within one hour, the bypass trip counter returns to 0 and the process should be repeated. A report of the swinger bypass is sent to the receiver if Bypass Reports is set to Yes. |
Zone Retard Delay
RETARD NO YES |
NO — Disable this option. YES — Allow the zone to operate with the Zone Retard Delay in System Options. The zone retard functions only in zone short conditions. The zone should remain shorted for the full length of the retard delay before the panel recognizes its condition. |
Presignal Keypads
PRESGNL KEYPADS: |
Enter the keypad addresses to sound a presignal tone during the time a zone is in retard delay. The presignal tone silences when the zone restores or the retard delay expires. |
Prewarn Keypads
PREWARN KEYPADS: |
Enter the keypad addresses you want to display ENTER CODE:- at the start of the Entry Delay. If you want the prewarn to sound at all 16 addresses, leave the default setting. The prewarn tone stops at the keypad where the first user code digit is entered. If no keys are pressed for five seconds or an invalid user code is entered, the prewarn tone resumes at that keypad. |
Chime
CHIME: NONE NONE DB DESC ASC |
Select one of the following tones to assign to a zone:
|
Entry Delay
ENTRY DELAY: |
Select the entry timer for this zone. Entry timers 1 to 4 are programmed in System Options. |
Cross Zone
CRS ZONE NO YES |
NO (default) — Disable this option. YES — Enable cross zoning for this zone. Cross zoning requires one or more armed zones to fault within a programmed time before an alarm report is sent to the receiver. See Cross Zoning Operation for more information. |
Priority
PRIORITY NO YES |
NO (default) — Disable this option. YES — Require the zone to be in a normal condition before its assigned area can be armed. |
Area Follower
FOLLOW AREA: 0 |
Enter the area number with the active Exit or Entry delay that Night, Day, Auxiliary 1, or Auxiliary 2 zones should follow. The default is 0. |
Zone Real-Time Status
ZONE REAL-TIME STATUS
|
NO (default) — Disable this option. YES — Send Real-Time Status reports, such as Door Open or Closed with the zone number, using Entré, the API connection, and Dealer Admin reporting. |
Traffic Count
TRAFFIC COUNT?
|
NO — Disable this option YES — Send reports to the receiver of the number of zone trips while in a disarmed state. The number of trips are included with the area closing message and reported to the monitoring center automation system. Traffic count data for the 10 lowest numbered zones is also sent to Virtual Keypad. |
Zone Audit Days
ZONE AUDIT DAYS:
|
Enter the number of days (0 to 365) allowed to elapse without the zone being tripped before a fault message is sent. The default is 0. The message is sent to the receiver(s) programmed to receive Supervisory/Trouble reports at 10:00 am following the expiration of the timer. Each time the zone is tripped, the Zone Audit Days timer restarts and begins to count down the number of days programmed. After the countdown expires, a fault message is sent and the Zone Audit Days timer restarts and begins to count down the number of days programmed. |
Lockdown
LOCKDOWN: NO YES |
NO (default) — Disable this option. YES — Trigger a lockdown when the zone is tripped. |
Report to tr
-
When you are finished, continue programming additional menus as needed, or press CMD until STOP displays, then press any select key or area to save the panel programming.
Program the Panel in Dealer Admin
Before You Begin
-
Verify the panel is connected to network
-
Log in to Dealer Admin.
-
Go to Customers, then select the System Name.
-
Go to Programming > Zone Information.
-
Configure the following options as needed:
|
Dealer Admin Field |
Description |
|---|---|
Zone Number
|
Select + Add Zone, then enter a Zone Number. Refer to the Zone Numbers Table for more information. |
Zone Name
|
Enter the zone name. |
Zone Location
|
If needed, enter a zone location name up to 32 characters that is separate from the zone name. Enter a description location for the zone, such as 2nd Floor East Wing. The zone location is only sent to the monitoring center to help dispatchers identify where an alarm is triggered and does not display at the keypad. |
Zone Type
|
Select one of the following zone types:
If you select Blank, Night, Day, Exit, Auxiliary 1, Auxiliary 2, or Arming as the zone type, assign the zone to an active area. If you select Fire, Panic, Holdup, Emergency, Supervisory as the zone type, it is a 24-hour zone that is always armed and no area assignment is needed. |
Area Assignment
|
Select an area to assign to the zone. |
Chime
|
Select one of the following tones to assign to a zone:
|
Follow Area
|
Select the area with the active Exit or Entry delay that Night, Day, Auxiliary 1, or Auxiliary 2 zones should follow. |
Sensor Type
|
|
Expander Serial Number
|
If you are using a zone expansion module, enter the 10-character serial number found on the module. |
V-Plex Serial Number
|
If you are using a V-Plex module, enter the serial number found on the module. |
AlarmVision Zone
|
Toggle OFF to disable this option. Toggle ON if you are programming an AlarmVision zone. |
Wireless
|
|
DMP Wireless
|
Toggle OFF to disable this option. Toggle ON if you are programming a DMP wireless zone. |
Serial Number
|
Enter the device’s serial number. |
Contact
|
Select Internal or External as the type of device contact. |
Contact Normally Open
|
Toggle OFF to allow the external contact to follow Normally Closed (N/C) operation. Toggle ON to allow the external contact to follow Normally Open (N/O) operation. |
Supervision Time
|
Select one of the following options that the zone should check in at least once during this time or a missing condition is indicated for that zone:
|
LED Operation
|
Toggle OFF to disable this option. Toggle ON to enable LED operation. The LED always operates if tampering is detected. |
Disarm Disable
|
Toggle OFF to disable this option. Toggle ON to disable Zone Tripped messages for the zone when the system is disarmed. |
PIR Pulse Count
|
If you are programming a PIR device, select the number of infrared pulses the PIR counts within 25 seconds before sending a Short message. |
PIR Sensitivity
|
If you are programming a PIR device, select one of the following PIR sensitivities: Low (default) — 75% sensitivity for harsh environments High — Maximum sensitivity |
PIR Pet Immunity
|
If you are programming a PIR device, choose if you want to enable pet immunity. |
Advanced
|
|
Swinger Bypass
|
Toggle OFF to disable this option. Toggle ON to allow the zone to be swinger bypassed by the panel according to the specifications programmed in Swinger Bypass Trips and Reset Swinger Bypass. The Bypass condition displays in the keypad Status List. |
Zone Retard Delay
|
Toggle OFF to disable this option. Toggle ON to allow the zone to operate with the Zone Retard Delay in System Options. The zone retard functions only in zone short conditions. The zone should remain shorted for the full length of the retard delay before the panel recognizes its condition. |
Presignal Keypads
|
Enter the keypad addresses to sound a presignal tone during the time a zone is in retard delay. The presignal tone silences when the zone restores or the retard delay expires. |
Prewarn Keypads
|
Enter the keypad addresses you want to display ENTER CODE:- at the start of the Entry Delay. If you want the prewarn to sound at all 16 addresses, leave the default setting. The prewarn tone stops at the keypad where the first user code digit is entered. If no keys are pressed for five seconds or an invalid user code is entered, the prewarn tone resumes at that keypad. |
Cross Zone
|
Toggle OFF to disable this option. Toggle ON to enable cross zoning for this zone. Cross zoning requires one or more armed zones to fault within a programmed time before an alarm report is sent to the receiver. See Cross Zoning Operation for more information. |
Entry Delay
|
Select the entry timer for this zone. Entry timers 1 to 4 are programmed in System Options. |
Priority Zone
|
Toggle OFF to disable this option. Toggle ON to require the zone to be in a normal condition before its assigned area can be armed. |
Traffic Count
|
Toggle OFF to disable this option. Toggle ON to send reports to the receiver of the number of zone trips while in a disarmed state. The number of trips is included with the area closing message and reported to the monitoring center automation system. Traffic count data for the 10 lowest numbered zones is also sent to Virtual Keypad. |
Zone Audit Days
|
Enter the number of days (0 to 365) allowed to elapse without the zone being tripped before a fault message is sent. The default is 0. The message is sent to the receiver(s) programmed to receive Supervisory/Trouble reports at 10:00 am following the expiration of the timer. Each time the zone is tripped, the Zone Audit Days timer restarts and begins to count down the number of days programmed. After the countdown expires, a fault message is sent and the Zone Audit Days timer restarts and begins to count down the number of days programmed. |
Arm Areas
|
Select which areas arm when the Arming zone is activated. |
Zone Real-Time Status
|
Toggle OFF to disable this option. Toggle ON to send Real-Time Status reports, such as Door Open or Closed with the zone number, using Entré, the API connection, and Dealer Admin reporting. |
Lockdown
|
Toggle OFF to disable this option. Toggle ON to trigger a lockdown when the zone is tripped. |
|
Actions |
|
|
Configure the following options for Disarmed Open, Disarmed Short, Armed Open, and Armed Short actions: |
|
Message
|
Select one of the following actions taken by the system when the zone is in the selected condition while the area is armed or disarmed:
Note: UL requirements prevent the Alarm (A) and Trouble (T) action for Fire zone types from being changed.
|
Output
|
Enter any Relay Output number to be activated by a zone condition. The default is 0. The output can be activated regardless of the Report to Transmit and if the zone is programmed as local. An output activated by an armed zone is turned off when the zone area is disarmed by a user. |
Output Action
|
Select one of the following output actions to assign to the relay:
|
-
When you are finished, select one of the following options:
-
-
If you are finished with all programming — Select Send All Changes at the top of the screen. This sends all programming changes to the panel.
-
If you are finished programming Zone Information only — Select the More icon
, then select Send Zone Information. This only sends zone programming changes to the panel.
-
Reference
Zone Numbers Table
|
Panel |
Programming Zone Number |
|---|---|
|
Onboard |
1-10 |
|
Keypad Bus |
Programming Zone Number |
|
1 |
11-14 |
|
2 |
21-24 |
|
3 |
31-34 |
|
4 |
41-44 |
|
5 |
51-54 |
|
6 |
61-64 |
|
7 |
71-74 |
|
8 |
81-84 |
|
9 |
91-94 |
|
10 |
101-104 |
|
11 |
111-114 |
|
12 |
121-124 |
|
13 |
131-134 |
|
14 |
141-144 |
|
15 |
151-154 |
|
16 |
161-164 |
|
1100 Series Wireless Products |
Programming Zone Number |
|
1144 Series Key Fob |
400-449 |
|
500-999* |
|
|
*This zone range is only valid when programming key fobs as 1-button or 2-button wireless panic zone. |
|
|
LX-Bus |
Programming Zone Number |
|
LX5 |
500-599 |
|
LX6 |
600-699 |
|
LX7 |
700-799 |
|
LX8 |
800-899 |
|
LX0 |
900-999 |
Zone Type Descriptions
-
- (Blank Zone) — By default, no actions are programmed to occur with the Blank zone. Ensure a zone name is entered to use this zone type. This zone type is not the same as an *UNUSED* zone.
-
NT (Night) — Controlled instant zone used for perimeter doors and windows and interior devices such as PIRs and Glassbreak detectors
-
DY (Day) — Used for emergency doors or fire exit doors to sound the keypad buzzer and display the zone name when the zone is faulted. Day zones also send alarm reports to the receiver during the system armed periods.
-
EX (Exit) — Initiates the Entry Delay timer when its assigned area is fully armed. The zone can also initiate an Exit Delay timer to allow a user to exit an area after the arming process starts.
-
FI (Fire) — Used for any type of powered or mechanical fire detection device. Typical applications are for smoke detectors, sprinkler flowswitches, manual pull stations, and beam detectors. Retard, cross zoning, and presignal options are available for the Fire zone type.
-
PN (Panic) — Used for connecting to mechanical devices that allow a user to signal an emergency alarm, including key fobs programmed as panic zones. Panic zones can provide either a silent or audible alarm with or without reporting to a monitoring center.
-
EM (Emergency) — Used for reporting medical or other non-panic emergencies to the monitoring center
-
SV (Supervisory) — Used to provide 24-hour zone supervision to devices associated with fire systems. Typical applications are tamper switches on Post Indicator Valves (PIVs), gate valves, and low and high temperature gauges.
-
A1 and A2 (Auxiliary 1 and Auxiliary 2) — Used like a Night zone to protect restricted areas within protected premises
-
AR (Arming) — Used to allow you to connect a keyswitch to a zone, and arm and disarm one or more areas
-
IN (Instant) — Used as a zone that does not follow Entry or Exit zones. Choose Instant if you need a zone that does not follow the Entry or Exit delay.
-
DB (Doorbell) — Used as a zone assigned to doorbells.
-
HU (Holdup) — Used as silent panics, which do not trigger audial or visual alerts on the keypad
Cross Zoning Operation
When the first cross zoned zone trips, the Cross Zone Time in System Options begins to count down. When a second cross zoned zone trips or the first zone trips a second time before the end of the countdown, the Bell Action assigned to the zone activates and the panel sends an alarm report for both zones.
If no other cross zoned zone trips before the cross zone time expires, the panel only sends a zone fault report to the receiver. Cross zoning is not compatible with all zone types. You cannot enable cross zoning for any Fire zones that have Zone Retard Delay set to Yes.